Wcc iii system features, Building # 2, Wcc iii technical guide 19-4 – WattMaster WCC III part 20 User Manual
Page 6
![background image](https://www.manualsdir.com/files/809321/content/doc006.png)
WCC III Technical Guide
19-4
19. POWER AND SWITCHABLE COMM BOARD
Diagram of WCC III System
The heart of the WCC III system consists of an Internet
Appliance referred to as the Master Communications Device
(WCC III - MCD) and the WCC III Operator Console which
consists of a standard computer with the Windows® XP-Pro/
Vista or Windows® 7 operating system, keyboard, mouse and
monitor (screen). The WCC III - MCD communicates with the
remote satellite controllers using a RS-485 two-wire with shield
communication loop.
The WCC III - MCD connects to the Internet via cable/DSL
modem/router. The WCC III - MCD can also be networked into an
existing network if desired.
NOTE:
WattMaster Controls does not assume responsibility
for any network connections or associated networking
problems. Please contract a computer network specialist for
specifi c network requirements. The WCC III - MCD is only
supported on Microsoft-type networks.
Figure 19-3: Diagram of the WCC III System
WCC III System Features
OE210
TYPICAL
SPACE
SENSOR
(X8 MAX)
ON/OFF RELAY
PUMPS, LIGHTS,
ETC.
8
7
SAT ADDRESS
2
1
4
8
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
C
H
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2
1
3 4
2
1
3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
8
7
SAT ADDRESS
2
1
4
8
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
C
H
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2
1
3 4
2
1
3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES
"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES
"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICD
Communications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS
1
STATUS
LOCAL SET
16
4
2
8
64
32
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
OE320
TUC-2R
OE331
TUC-5R+
W
A
R
M
E
R
C
O
O
L
E
R
OVR
OE213
TYPICAL
SPACE
SENSOR
OE421- SAT III
CONTROLLER
OE454/O 455/OE456
E
SAT 3C/D/F
CONTROLLER
W
A
R
M
E
R
C
O
O
L
E
R
OVR
OE213
TYPICAL
SPACE
SENSOR
WCC II TO WCC III
GLOBAL BRIDGE
WCC III-MCD
SINGLE PULSE
INPUT FROM
POWER METER
UP TO 32 TOTAL
FAN COIL, HEAT PUMP
PD VAV TERMINAL UNITS
PI VAV TERMINAL UNITS
PARALLEL FAN BOX, ETC.
VAV BOX
16 OUTPUTS
PER SAT III
UP TO 60 TOTAL SAT III
OR SAT 3C/D/F/P PER LOOP.
THERE ARE 4 POSSIBLE
SAT III RS485
COMMUNICATIONS LOOPS
(UP TO 239 SAT III MAXIMUM)
TO THE ISP
(INTERNET SERVICE PROVIDER)
CONNECTION TO THE INTERNET
(BY OTHERS)
HIGH SPEED CABLE
MODEM / ROUTER
ETHERNET
CABLE
Optional V-OUT Board
( 8 RELAY OUTS)
(2 PER SAT III)
Optional B-INPUT Board
( 8 BINARY INPUTS)
(2 PER SAT III)
HSS PORT
HEAT PUMP
SAT II
SAT III
PROGRAM SOCKET
ADDRESS
24C128
PCF8583
LT1785
WATTMASTER CONTROLS INC
CONNECTION
TO OLD WCC II
MANCHESTER
COMM LOOP
1
2
4
8
16
32
64
128
ADDRESS
SATIII-P
TEST
LOCAL
L DIS
OPT 1
OPT 2
OPT 3
R
T
24 VAC
GND
OPTIONS
PULSE INPUTS
“P” MODE ADDRESSING NOTES
SAT III ADDRESSING STARTSAT
ADDRESS NUMBER 8.
EACH "P" MODE SAT III TAKES UP
(8) SAT III LOGICAL ADDRESSES.
THERE ARE ONLY (8) USED ACTIVE
INPUTS PER SAT 3P.
ANALOG INPUT #1 (PULSE INPUT #1)
ON EACH SAT III ADDRESS IS ACTIVE.
ALL OTHER INPUTS AND OUTPUTS ON
THE SAT 3P ARE NOT FUNCTIONAL.
TOTAL WIRING FOR EACH INPUT NOT
TO EXCEED 100 FEET.
USE 18 GAUGE TWISTED PAIR WITH
SHIELD FOR EACH PULSE METER
CONNECTION.
CONNECT THE SHIELD WIRE TO GND.
HSS PORT
MULTIPLE PULSE
INPUTS FROM
POWER METERS
OE455-P
SAT 3P
CONTROLLER
PL102224
POWER AND
SWITCHABLE COMM
USUALLY ONE
OR TWO PER
FLOOR
SAT COMM LOOP
SAT COMM LOOP
SAT COMM LOOP
TUC COMM LOOP
B B
PL102224
POWER AND
SWITCHABLE COMM
USUALLY ONE
OR TWO PER
FLOOR
FIBER OPTIC LINES
MAXIMUM OF 2.5 MILES
(USES "ST" CONNECTORS)
BUILDING # 2
8
7
SAT ADDRESS
2
1
4
8
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
C
H
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2
1
3 4
2
1
3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
OE421- SAT III
CONTROLLER
8
7
SAT ADDRESS
2
1
4
8
WattMaster Controls Inc.
BINARY
INPUTS
BINARY
INPUTS
L8
ON OFF
128
32
16
64
L4
L3
L2
L1
L6
L5
L7
L11
L12
ON OFF
L10
L9
ON OFF
L15
L16
L14
L13
C
H
4
3
5
6
2
1
LOCAL SET
STATUS 2
STATUS 3
STATUS 1
HSS XMIT
LOCAL SET
LOCAL SET DISABLE
BATT ON/ OFF
PULSE INPUT
OPTION 1
TEST
OPTION 3
OPTION 2
ON OFF
STATUS
HSS REC
SAT XMIT
SAT REC
ANALOG INPUT
JUMPER SELECTION
CURRENT
INPUT
THERMISTOR
INPUT
0 TO 10V
INPUT
0 TO 5V
INPUT
0 TO 1V
INPUT
PROGRAMMABLE CONTROLLER
SAT III
H
C
COM
CHANNEL
2
1
3 4
2
1
3 4
5 6 7 8
5 6 7 8
V
OUT
GND
L
O
A
D
+V
ATI
OE421- SAT III
CONTROLLER
"D" MODE
"C" MODE
"C" MODE ADDRESSING NOTES
"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.
"D" MODE ADDRESSING NOTES
"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.
SAT IIICD
Communications Interface
TUC XMIT
ON OFF
ON OFF
SAT ADDRESS
1
STATUS
LOCAL SET
16
4
2
8
64
32
128
LOCAL SET DISABLE
OPTION 2
LOCAL SET
OPTION 1
TEST
BATT ON/ OFF
TUC REC
SAT XMIT
SAT REC
OE320
TUC-2R
W
A
R
M
E
R
C
O
O
L
E
R
OVR
OE213
TYPICAL
SPACE
SENSOR
OE455
SAT 3D
CONTROLLER
VAV BOX
PL102335
RS-485 TO FIBER
OPTIC ADAPTER
USED IN MULTIPLES
OF TWO
PL102335
RS-485 TO FIBER
OPTIC ADAPTER
SAT COMM LOOP
SAT COMM LOOP
SAT COMM LOOP
UP TO 32 TOTAL
FAN COIL, HEAT PUMP
PD VAV TERMINAL UNITS
PI VAV TERMINAL UNITS
PARALLEL FAN BOX, ETC.
TUC COMM LOOP
OPTION 4
OPTION 3
OPTION 4
OPTION 3