20-9
20. GLOBAL BRIDGE BOARD INSTALLATION
Please note the following:
•
The later Manchester Communication Board will
need to have the 50 ohm load resistors installed on
it instead of the zero ohm jumper.
•
Location R24 and R25 should have a 50 ohm load
resistor installed.
•
A zero ohm jumper has a single Black band on it.
A 50 ohm resistor should have the color code of
“GREEN” “BROWN” “BLACK” “GOLD”.
Figure 20-6: SAT II Manchester Board Jumpers
P
P