Warning codes, System parameters – Watson-Marlow 621 Trio User Manual
Page 9
9
Warning Codes
In the event of a warning, the inverter display will flash. The last warning to occur is stored in parameter P931.
Warning
Cause
Corrective action
002
Current limit active
Check whether the motor power corresponds to the inverter power.
Check that the cable length limits have not been exceeded.
Check motor cable and motor for short-circuits and earth faults.
Check whether the motor parameters (P080-P085) correspond with the motor
being used.
Check the stator resistance (P089).
Increase the ramp start up time (P002).
Reduce the boost set in P078 and P079.
Check whether the motor is obstructed or overloaded.
003
Voltage slip active
004
Slip limit exceeded.
005
Inverter overtemperature
Check that the ambient temperature is not too high.
(heatsink)
Check that the air inlet and outlet are not obstructed.
Check that the inters integral fan is working.
006
Motor over-temperature
Check if motor is overloaded.
Check that P087 has not been set to 1 without a PTC being connected.
010
Use power supply- current limit
018
Auto re-start after fault (P018)
is pending
WARNING: The inverter may start at any time.
075
Braking resistor-hot
System Parameters
Note: In the following parameter table:
l
Indicates parameters that can be changed during operation.
¶¶¶
Indicates that the value of this factory setting depends on the rating of the inverter.
If parameters are changed accidentally, all parameters can be reset to their default values by setting parameter P944 to 1 and
then pressing P.
Parameter Function
Default
Your setting
P001
Operating dis[lay
-
P001
l
Dis[lay mode
0
P002
l
Ramp up time (seconds)
10.00
P003
l
Ramp down time (seconds)
25.00
P004
l
Smoothing (seconds)
0.0
P005
l
Digital frequency setpoint (Hz)
50.00
P006
Frequency setpoint source selection
1
P007
Keypad control
0
P009
l
Parameter protection setting
0
P011
Frequency setpoint memory
0
P012
l
Minimum motor frequency (Hz)
0.00
P013
l
Maximum motor frequency (Hz)
50.00
P014
l
Skip frequency 1 (Hz)
0.00
P015
l
Automatic restart after mains failure
0
P016
l
Start on the fly
0
P017
l
Smoothing type
1
P018
l
Automatic restart after fault
0
P019
l
Skip frequency bandwidth (Hz)
2.00
P020
Flying start ramp time (seconds)
25.0
P021
l
Minimum analogue frequency (Hz)
0.00
P022
l
Maximum analogue frequency (Hz)
50.00
P051
Selection control function (DIN1 - terminal 5) fixed
1
frequency 3 or binary fixed frequency bit 0
P052
Selection control function (DIN2 - terminal 6) fixed
2
frequency 2 or binary fixed frequency bit 1