8

Fault Codes

In the event of a failure, the inverter switches off and a fault code can be viewed on the OPm2 display. The last fault that occurred is
stored in parameter P930. e.g. ‘0003’ indicates that the last error was F003.

Fault Code Cause

Corrective Action

F001

Over voltage

Check whether supply voltage is within the limits indicated on the rating plate.
Increase the ramp down time (P003).
Check whether the required braking power is within the specified limits.

F002

Over current

Check whether the motor power corresponds to the inverter power.
Check the motor for short-circuits and earth faults.
Check whether the motor parameters (P081 - P085) correspond with the motor
being used.
Check the stator resistance (P089).
Increase the ramp-up time (P002).
Reduce the boost set in P078 and P079.
Check whether the motor is obstructed or overloaded.

F003

Overload

Check whether the motor is overloaded.

F005

Inverter over temperature

Check that the ambient temperature is not too high.

(internal PTC)

Check that the air inlet and outlet are not obstructed.

F008

USS protocol timeout

Check the serial interface.
Check the settings of the bus master and P091 - P093.
Check whether the timeout interval is too short (P093).

F010

Initialisation fault/

Check the entire parameter set. Set P009 to ‘0000’ before power down.

Parameter loss*

F011

Internal interface fault*

Switch off power and switch on again.

F012

External trip (PTC)

Check if motor is overloaded.

F013

Programme fault*

Switch off power and switch on again.

F018

Auto-restart after fault

Automatic re-start after fault (P018) is pending.
WARNING: The inverter may start at any time.

F030

PROFIBUS link failure

Check the integrity of the link.

F031

Option module to link failure

Check the integrity of the link.

F033

PROFIBUS configuration error

Check the PROFIBUS configuration.

F036

PROFIBUS module watchdog
trip

Replace PROFIBUS module.

F074

Motor over temperature

Check that the motor current does not exceed the value set in P083.

by I

2

t calculation

F106

Parameter fault P006

Parameterise fixed frequency(ies) and/or motor potentiometer on the digital
inputs.

F112

Parameter fault P012/P013

Set parameter P012 < P013.

F151-F153 Digital input parameter fault

Check the settings of digital inputs P051 to P053.

F188

Automatic calibration failure

Motor not connected to inverter - connect motor.
If the fault persists, set P088 = 0 and then enter the stator resistance of the
motor into P089 manually.

F201

P006 = 1 while P201 = 2

Change parameter P006 and/or P201.

F212

Parameter fault P211/P212

Set parameter P211 < P212.

* Ensure that the wiring guidelines to minimise the effects of EMI have been complied with.

When the fault has been corrected the inverter can be reset. To do this press button P twice (once to display P000 and the second
time to reset the fault), or erase the fault via a binary input (see parameters P051 - P053) or via the serial interface.