beautypg.com

704u calibration procedure, Remote auto-manual switch and, Ttl option – Watson-Marlow 704U User Manual

Page 5: 12 remote auto-manual switch and ttl option

background image

Watson-Marlow Bredel E-Manuals

http://www.watson-marlow.it/pdfs-global/m-704su-gb-03.htm[10/07/2012 14:21:14]

be used in conjunction with a DC voltmeter, (max 30V DC).

(Refer to the 25 pin terminal strip wiring detail as an

example of control circuitry.) Circuit impedance 100kOhms.

Polarity set for non-inverted response. Reverse polarity for

inverted response.

For current modes the same DC source can be used in

conjunction with a DC milliampere meter, (maximum

32mA). (See 25 pin terminal strip detail.) Circuit

impedance 250Ohms. Polarity set for non-inverted

response. Reverse polarity for inverted response.

Never apply mains voltage across any pins on the 25-pin cage clamp

connector. Up to 30V may be applied across pins 4 and 17, and 5V TTL

on pins 7 and 5, but no voltage should be applied across other pins.

Permanent damage not covered by warranty may result. Do not use the

mains power switch to control the 704U pump for a high repetition of

stop/starts. The auto-control facility should be used.

11 704U Calibration procedure

Turn the signal offset potentiometer (20 turn potentiometer) clockwise until the slider
traverse limit is reached and is signified by a clicking noise. Now turn the potentiometer
10 turns counter-clockwise. Repeat for the signal range potentiometer. This ensures
correct potentiometer set-up for calibration.
Set the process signal offset.
Turn the signal offset potentiometer clockwise to set the pump shaft speed to the
desired minimum.
Set the process signal at its upper range limit (not exceeding 30V or 32mA).
Turn the signal range potentiometer (marked "Range" on back panel) clockwise to set
the drive shaft speed to the desired maximum.

If the process signal or pump speed are set above their designated maximums the pump

will be overloaded which is signified by the signal overload indicator illuminating. The Aut

symbol will flash on the keypad. This is an indication of the limiting control and speed

levels of the drive. Reset to operate within these levels.

Repeat the procedure until pump response coincides exactly with the process signal.

12 Remote auto-manual switch and TTL option

Stop/Start

Connect remote switch between pins 7 and 15 of the 25-pin cage clamp connector.

Alternatively a TTL compatible logic input (Low 0V, High 5V) may be applied to pin 7. Low

input stops the pump, high input runs the pump. With no connection, the pump will default

to running. To invoke either remote stop or inverted remote stop, when switching power to

the pump using the pump on/off switch, press Stop and CW/CCW keys simultaneously.
The pump will indicate its current mode of switching for 2 seconds.

indicates standard

remoted switching,

indicates inverted remote switching.

This manual is related to the following products: