beautypg.com

Troubleshooting, Page 13, For problem a/c for problem heat – Venstar T1010 Installation User Manual

Page 14: Auto cool, Heat

background image

R

G

W

Y

C

TR300-10w

R

G

W

Y

C

TR300-10w

For Problem A/C

For Problem Heat

SYMPTOM: When using 4 wires (R, G, W, Y),
the air conditioning equipment tries
repeatedly to turn on, but cannot. At
times the display dims or disappears.
CAUSE: There is not enough power available
to "power share".
REMEDY: Connect a 270 ohm, 10 watt power
resistor at the furnace as shown below.

TROUBLESHOOTING

SYMPTOM: The air conditioning does not
attempt to turn on.
CAUSE: The compressor timer lockout may
prevent the air conditioner from
turning on, for a period of time.
REMEDY: See page 12 of the Owner's Manual
and configure step #9 to defeat the 5-
minute compressor lockout.

SYMPTOM: The display is blank.
CAUSE: Lack of proper power.
REMEDY: Make sure power is turned on to
the furnace and 24vac between R & W.
If C is used, 24vac between R & C.

AUTO

COOL

76

HEAT

68

AUTO

COOL

76

HEAT

68

AUTO

COOL

76

HEAT

68

Page 13

This manual is related to the following products: