Pcs-com in-line and t-splice kit, Power connection for flx-bc with braid only – Thermon PCS-COM User Manual
Page 5
4
3.3.
Feed cable and ground through expediter
base as shown. Feed cable and ground
lead through grommet (above the crimp).
3.2.
Trim braid to approximately 76mm (3”).
Crimp 12/10 AWG compression lug to
ground braid and ground lead.
3.1.
Separate braid strands at edge of overjacket
and pull cable through opening.
Ground Lead Wire
12/10 AWG
Crimp
Expediter
Base
Grommet
Ground
Lead
Cable
152mm
(6”)
Power connection for FLX-BC with braid only.
76mm
(3”)
Braid
3.4.
Slide expediter toward pipe and secure
using two (2) circumferential bands of
19mm (3/4”) wide tape.
3.5.
Place UL® label provided as shown,
locate on opposite side from rectangular
side opening.
Pip
e H
ea
tin
g C
ab
le 1
34
N
HS
X
® or
FL
X™
H
ea
tin
g C
ab
le S
ys
tem
Ins
tall
C
ab
le p
er N
EC
A
rti
cle
42
7
Th
erm
on
M
an
ufactu
rin
g C
o.
10
0
Th
erm
on
D
r., San Marco
s,
Te
xas 7866
6
1-8
00
-7
30
-4
32
8
P
N
2
74
00
Tape Provided
Separately
UL Label
3.6.
Cut and remove primary insulation jacket.
3.7.
Skive outside of black matrix
.
3.8.
Cut V-notch in matrix and pull bus wires
from matrix. Cut and remove center
matrix.
Do not cut bus wire strands.
117mm
(4-5/8”)
Bus Wire
Primary Insulation
Ground Lead
Matrix
Ground Lead
Ground Lead
Ground Lead
Black Matrix
Matrix
PCS-COM In-line and T-Splice Kit
12/10 AWG