KSR-EJK expansion joint kit is designed to allow cable to cross
a concrete expansion or construction joint. When installed, the
kit will allow normal expansion and contraction of the substrate
without straining or damaging the cable.
Installation Precautions . . .
• The kit instructions should be used in conjunction with installation
instructions for the heating cable and other accessory items.
• Keep ends of heating cable and kit components dry before and
during installation.
KSR-EJK
2
Item
Quantity
Description
Split Corrugated Tubing
2
Self Vulcanizing Tape
Kit Contents . . .
1.
Insert cable into corrugated tubing through split in tubing. Rotate
corrugated tubing until split is facing downward.
Split at Bottom
Corrugated Tubing
KSR Cable
Corrugated Tubing
KSR Cable
Self Vulcanizing Tape
2.
Wrap self vulcanizing tape around heating cable and each end of split
corrugated tubing.
75mm
(3”)
50mm
(6”)
200mm
(8”)
50mm
(2”)
Sand Fill
Concrete
Reinforcement
Bar
Expansion Joint
Installation Instruction . . .
3.
Typical heating cable layout should be routed to avoid crossing
expansion, crack, or construction joints. If crossing a joint is required,
the cable and protective tube should be looped beneath the joint, with
the cable attached to the concrete reinforcing bar at each end.
Tie Wrap