The ET-6C Kit is used for end circuit termination of BSX,

RSX, and VSX

self-regulating heating cables.

IP66 NEMA/Type 4X
Ordinary & Hazardous Locations
Listed Heat Tracing Cable System 137M
Certifications vary by cable type. See product
specification sheets for additional information.

Tools Required . . .

Warnings

. . .

• Due to the risk of electrical shock, arcing and fire caused

by product damage or improper usage, installation or

maintenance, a ground-fault protection device is required.

• Installation must comply with Thermon requirements (in-

cluding form PN 50207 for Ex systems) and be installed in

accordance with the NEC, CEC, or any other applicable

national and local codes.

• Component approvals and performance ratings are based

on the use of Thermon specified parts only.

• Keep ends of heating cable and kit components dry before

and during installation.

• Store in a dry location.

ET-6C

Installation Instructions

1

2

Kit Contents . . .

Item Quantity

Description

1

1

End Cap

2

1

RTV Tube

Certifications/Approvals

1

. . .

Cable Take-off

for BSX, RSX, TSX, VSX

Installation Instructions

for BSX, RSX, VSX

1.

Cut off end of cable.

2.

Cut and remove overjacket.

3.

Trim away exposed braid from cable.

4.

Fill the end cap with RTV sealant and

apply a circumferential bead to cable

[minimum of 3 mm (0.12”) wide]. Slide

end cap onto end of cable.

Specifications and information are subject to change without notice. Form PN50085-0614