Terminator, Ecm-p-xp, Installation procedures – Thermon ECM-P-XP User Manual

Page 4

background image

4

11.

Mount junction box base on expediter.
Make sure to align slots to properly
orient junction box base. Tighten nut
with Terminator-LN-Tool. If mounting
horizontally, threaded gland holes must
face downward.

12.

Install M25 power gland (order
separately) and M25 blind plug.

13.

Install power cable.

14.

Install electronic control module and
complete system wiring. Terminal set
screws shall be tightened to a torque
value of 1,4 Nm (12,4 lb-in). See page 5
for wiring details. Set modules electronic
control and/or control limiter at desired
setpoints.

16.

Use screwdriver to ratchet on junction
box lid. Lid will rotate 30 degrees. Install
junction box lid and twist hand tight.
Insert screwdriver into ratchet slots
located on side of junction box base.

17.

Lid latch mechanism fully engaged. To
remove lid, repeat step 16 but in the
opposite direction.

The Heat Tracing Specialists

®

15.

Use the rotary switches for settling
Control and Limit Temperature,
Celsius or Fahrenheit and Auto or
Manual reset (Control switches on
Type "C", Limiter switches on Type
"L" and both on Type "CL").

Terminator

TM

ECM-P-XP

INSTALLATION PROCEDURES

1725 II 2 GD Ex eb mb [ib]ib IIC T4, Ex tb IIIC T135°C
SIRA 12ATEX5239X

IP66

-60

°C Ta + 55°C

IECEx SIR 12.0103X Ex eb mb [ib]ib IIC T4, Ex tb IIIC T135°C

PN 27673

D

o n

ot o

pen

while

energized. See installa

tion

in

str

uc

tio

ns

.

Te

rm

inator EC

M

Fo

r u

se

as

an

adj

ustable

electronic c

ontro

l m

od

ule

10.

Fix expediter, RTD, and lead wire to
pipe.