Title: Southern States –

LLS-I-2000, LLS-II-2000 and LLS-II-3000
Load and Line Switchers

Product Specification Guide

Page 2 of 5

Publication No.: PSG-805-080109

1.0 SCOPE

This specification covers the design, manufacture, and testing of outdoor load and line
switchers.

2.0 STANDARDS

All outdoor load and line switchers shall be designed, manufactured, assembled, and
tested in accordance with the latest applicable ANSI, NEMA, IEEE, and ASTM
standards and guidelines. If there are any conflicts between the ANSI, NEMA, IEEE, or
ASTM standards and this specification the specification shall govern.

3.0 DESIGN REQUIREMENTS

3.01 Service

Conditions

The load and line switcher shall be suitable for outdoor installation in electric
power substations and on transmission line applications under the following
conditions:

3.01.01 Temperature

The load and line switcher shall perform in an ambient temperature
range of -40

o

C through +50

o

C.

3.01.02 Altitude

The load and line switcher shall perform at elevations up to 3,300 feet.

3.01.03 Additional Requirements

If any site specific service conditions not covered in sections 3.01.01 and
3.01.02 exist (e.g. extreme cold temperature installation, high altitude
installation, etc.) they will be defined in the quotation request.

3.02 Ratings

Design Characteristics

LLS-I-2000

LLS-II-2000

LLS-II-3000

Maximum Voltage

38 kV – 72.5 kV

72.5 kV -170 kV

245 kV

72.5 kV -170 kV

245 kV

Load Breaking Capability

2000 A

2000 A

2000 A

3000 A

2000 A

Line Dropping Capability

300 A

300 A

200 A

300 A

200 A

Loop Splitting Capability

2000 A

2000 A

2000 A

3000 A

3000 A

Nominal Operating Pressure

65 psig at 20ºC

55 psig at 20ºC

for 72.5 kV, 65

psig at 20ºC for

123 kV-170 kV

65 psig at 20ºC

55 psig at 20ºC

for 72.5 kV, 65

psig at 20ºC for

123 kV-170 kV

65 psig at 20ºC

Full Load Operations

2000

2000

2000

2000

2000