Title: Southern States –
LLS-I-2000, LLS-II-2000 and LLS-II-3000
Load and Line Switchers
Product Specification Guide
Page 2 of 5
Publication No.: PSG-805-080109
1.0 SCOPE
This specification covers the design, manufacture, and testing of outdoor load and line
switchers.
2.0 STANDARDS
All outdoor load and line switchers shall be designed, manufactured, assembled, and
tested in accordance with the latest applicable ANSI, NEMA, IEEE, and ASTM
standards and guidelines. If there are any conflicts between the ANSI, NEMA, IEEE, or
ASTM standards and this specification the specification shall govern.
3.0 DESIGN REQUIREMENTS
3.01 Service
Conditions
The load and line switcher shall be suitable for outdoor installation in electric
power substations and on transmission line applications under the following
conditions:
3.01.01 Temperature
The load and line switcher shall perform in an ambient temperature
range of -40
o
C through +50
o
C.
3.01.02 Altitude
The load and line switcher shall perform at elevations up to 3,300 feet.
3.01.03 Additional Requirements
If any site specific service conditions not covered in sections 3.01.01 and
3.01.02 exist (e.g. extreme cold temperature installation, high altitude
installation, etc.) they will be defined in the quotation request.
3.02 Ratings
Design Characteristics
LLS-I-2000
LLS-II-2000
LLS-II-3000
Maximum Voltage
38 kV – 72.5 kV
72.5 kV -170 kV
245 kV
72.5 kV -170 kV
245 kV
Load Breaking Capability
2000 A
2000 A
2000 A
3000 A
2000 A
Line Dropping Capability
300 A
300 A
200 A
300 A
200 A
Loop Splitting Capability
2000 A
2000 A
2000 A
3000 A
3000 A
Nominal Operating Pressure
65 psig at 20ºC
55 psig at 20ºC
for 72.5 kV, 65
psig at 20ºC for
123 kV-170 kV
65 psig at 20ºC
55 psig at 20ºC
for 72.5 kV, 65
psig at 20ºC for
123 kV-170 kV
65 psig at 20ºC
Full Load Operations
2000
2000
2000
2000
2000