Refrigeration cycle components, Troubleshooting and repair – DENSO CORPORATION CLASSIC PLUS 26 User Manual
Page 42
TROUBLESHOOTING AND REPAIR
34
Refrigeration Cycle Components
B. Removal of Refrigeration Cycle Components
ƽCAUTION:
1.
Before any refrigeration cycle component can be replaced, it is necessary to recover the refrigerant
using standard recovery procedures and equipment.
2.
To prevent oxidation, dry nitrogen should be conducted (flow rate 1 liter/min) through the pinch-off
tube during any brazing operation.
3.
During any component replacement involving brazing, shield nearby parts with a steel plate,
asbestos, etc., to protect them from the flame.
(1) Evaporator
(2) Capillary tube
(3) Condenser
(4) Compressor
NOTE: Hold the compressor body, not the tube, when carrying the compressor.
A
C
B
E
F
D
PART REPLACED DISCONNECT AT:
Compressor
A & B
Condenser
A & C
Capillary tube
D & E
Evaporator
E & F
Removal of Refrigerant Cycle Components (Refer to 20.B.)