3.7.3 SetSensorType()
Function:
Declares the sensor type to be interfaced to the specified channel.
The sensor type is specified by means of a Logical Sensor Definition Code (LSDC). Not all LSDC values are
supported by all Smart A/D™ products; refer to your hardware documentation for a complete list of supported
sensor types and input rangesUse of illegal or unsupported LSDC values may cause unpredictable results.
Do not confuse the LSDC with the native SDC that may be discussed in your hardware documentation. The LSDC
values are valid for all Smart A/D™ models, while the native SDC values, which are described in your hardware
documentation, are specific to each product model and may deviate from one model to another.
Prototype:
void SetSensorType( long hBD, long channel, long LSDC );
Parameter
Type
Description
hBD
long
Board handle.
channel
long
Sensor channel number to be affected.
LSDC
long
Logical Sensor Definition code from the following table:
Input Class
LSDC
Input Range / Sensor Type
Voltage Input
1
±10V
3
±5V
5
±500mV
6
±100mV
Thermocouple
34
B
33
C
8
E
10
J
12
K
32
N
18
R
16
S
14
T
RTD
41
Copper 10 Ohm
35
Nickel 120 Ohm
36
Nickel 200 Ohm
37
Nickel 1K Ohm (1353 Ohms @ 60 DegC)
42
Nickel 1K Ohm (1285 Ohms @ 60 DegC)
20
Platinum 100 Ohm 385 (0.1C res, full sensor range)
38
Platinum 100 Ohm 385 (0.0125C res, range -200:+400C)
22
Platinum 100 Ohm 392 (0.1C res, full sensor range)
39
Platinum 100 Ohm 392 (0.0125C res, range -200:+400C)
43
Platinum 1K Ohm (1422.9 Ohms @ 110 DegC)
Thermistor
24
10K with autorange
40
10K on fixed 600K ohm range
Current Loop
25
4-20 mA
Gage
26
Strain/pressure gage