Exhaust Measurement
On account of the construction-dependent design of the
exhaust connection (connection nozzle with secondary
air openings), it is not possible to perform a correct ex-
haust analysis in a conventional manner in the exhaust
pipe behind the exhaust connection.
For the performance of the exhaust analysis the sensor
of the exhaust-measurement device must be placed in
the centre of the pipe socket of the heat exchanger.
The measurement sensor is placed through the appro-
priate lateral secondary air opening in the exhaust con-
nection in the existing measurement opening in the pipe
nozzle of the combustion chamber (see drawing below).
Adjustments of the burner head
◊
Distance nozzle - air flow plate 4 mm
◊
Distance nozzle - electrode tip 2 mm
◊
Distance centre of nozzle - electrode tip 8 mm
◊
Distance between the electrode tips 3-4 mm
Coarse adjustments of the air slide plate
1. Loosen the safety screw S.
2. Set the air slide plate L by turning to an opening
width of ca. 25 mm.
3. Tighten the safety screw again.
S
L
Fine adjustment of air slide plate
Fine adjustment of air slide plate by means of CO
2
indi-
cator and soot pump.
CO
2
- value: approx. 10 - 13 %
Soot figure: 0 - 1 (by Bacharach)
4. When maintenance has been carried out re-
assemble all parts carefully in reverse order.
5. Pre-set air flow plate, air slide plate and the ignition
electrode distance according to the approximate indi-
cations.
4
2
3-4
8
air slide
plate
air flow
plate
exhaust
connection
measurement
sensor
pipe socket
measurement
opening
Drawing top-view
exhaust
connection
measurement
sensor
pipe socket
auxiliary air
opening
Service and Guarantee
Any claims under guarantee regarding materials can be
accepted only when the orderer or his customer has
filled in completely the “guarantee certificate” which is
enclosed with every REMKO-heater and has returned it
to REMKO GmbH & Co. KG in due time after the unit’s
sale and commissioning.
The units are factory tested on faultless function. If any
failures occurs though which cannot be eliminated by the
operating person, please contact your dealer or contact
person.
An operation/use other than that indicated in these in-
structions is prohibited!
In the case of non-observation we will not be held re-
sponsible and our guarantee will become void.