Equipment data, Appendix: 12.2 equipment data – Dimplex SI 75ZS User Manual
Page 15
15
APPENDIX: 12.2 EQUIPMENT DATA
Equipment Data
EQUIPMENT DATA for brine-to-water heat pumps for heating purposes
1
TYPE AND COMMERCIAL DESCRIPTION
..50ZSN
..75ZSN
..100ZSN
2
MODEL
2.1
Enclosure type acc. to EN 60 529
IP 21
IP 21
IP 21
2.2
Installation site
indoors
indoors
indoors
3
PERFORMANCE DATA
3.1
Operating temperature limits:
Heating water supply
°C
max. 60
max. 60
max. 60
Brine (heat source)
°C
-5 to +25
-5 to +25
-5 to +25
Antifreeze agent
monoethylene glycol
monoethylene glycol
monoethylene glycol
Minimum brine concentration (-13°C freezing temperature)
25%
25%
25%
3.2
Heating water temperature difference at B0 / W35
K
8,9
9,9
9,7
3.3
Heating capacity / coeff.of perform.
at B-5 / W55
1)
kW / ---
5)
37,5 / 2,4
59,8 / 2,3
76,2 / 2,5
kW / ---
6)
15,0 / 2,1
30,1 / 2,2
33,6 / 2,4
at B0 / W50
1)
kW / ---
5)
43,8 / 3,0
69,8 / 2,9
87,9 / 3,1
kW / ---
6)
18,5 / 2,5
33,3 / 2,8
39,1 / 2,8
at B0 / W35
1)
kW / ---
5)
46,7 / 4,5
75,2 / 4,4
96,3 / 4,6
kW / ---
6)
23,0 / 4,4
37,6 / 4,3
48,4 / 4,6
3.4
Sound power level
dB(A)
65
69
71
3.5
Sound pressure level at a distance of 1 m
dB(A)
50
54
55
3.6
Heating water flow rate at internal pressure difference
m³/h / Pa
4,5 / 2000
6,5 / 2500
8,5 / 3600
3.7
Brine flow rate at internal pressure difference (heat source)
m³/h / Pa
12,8 / 15700
20,5 / 17800
24,0 / 18600
3.8
Refrigerant; total charge weight
Type / kg
R404A / 8,6
R404A / 12,6
R404A / 20,5
4
DIMENSIONS; CONNECTIONS AND WEIGHT
4.1
Equipment dimensions without connections 4)
H x W x L mm
1890 x 1350 x 750
1890 x 1350 x 750
1890 x 1350 x 750
4.2
Equipment connections for heating system
inches
G 1 1/2'' i/ext.
G 2'' i/ext.
G 2'' i/ext.
4.3
Equipment connections for heat source
inches
G 2 1/2'' i/ext.
G 2 1/2'' i/ext.
G 3'' i/ext.
4.4
Weight of transport unit(s) incl. packaging
kg
486
571
652
5
ELECTRICAL CONNECTION
5.1
Nominal voltage; fusing
V / A
400 / 50
400 / 63
400 / 80
5.2
Nominal power consumption
1)
B0 W35
kW
10,45
16,95
20,93
5.3
Starting current with soft starter
A
56
105
120
5.4
Nominal current B0 W35 / cosϕ
5)
A / ---
18,9 / 0,8
30,58 / 0,8
37,8 / 0,8
6
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
3)
3)
3)
7
OTHER DESIGN CHARACTERISTICS
7.1
Water inside equipment protected against freezing
2)
yes
yes
yes
7.2
Performance settings
2
2
2
7.3
Controller internal / external
internal
internal
internal
1)
2)
The heating circulating pump and the controller of the heat pump must be on standby at all times.
3)
See EC Declaration of Conformity
4)
Please keep in mind that additional space is required for pipe connections, operation and maintenance.
5)
2-compressor operation
6)
1-compressor operation
Subject to technical modifications
Issued: 02.11.2005
These data characterize the size and performance capability of the system. For economic and energetic reasons, additional factors such as balance point and control need to be
taken into consideration. Abbreviations have the following meaning, e.g. B10 / W55: heat source temperature 10 °C and heating water supply temperature 55 °C.