beautypg.com

Equipment data, Appendix: 12.2 equipment data – Dimplex SI 75ZS User Manual

Page 15

background image

15

APPENDIX: 12.2 EQUIPMENT DATA

Equipment Data

EQUIPMENT DATA for brine-to-water heat pumps for heating purposes

1

TYPE AND COMMERCIAL DESCRIPTION

..50ZSN

..75ZSN

..100ZSN

2

MODEL

2.1

Enclosure type acc. to EN 60 529

IP 21

IP 21

IP 21

2.2

Installation site

indoors

indoors

indoors

3

PERFORMANCE DATA

3.1

Operating temperature limits:

Heating water supply

°C

max. 60

max. 60

max. 60

Brine (heat source)

°C

-5 to +25

-5 to +25

-5 to +25

Antifreeze agent

monoethylene glycol

monoethylene glycol

monoethylene glycol

Minimum brine concentration (-13°C freezing temperature)

25%

25%

25%

3.2

Heating water temperature difference at B0 / W35

K

8,9

9,9

9,7

3.3

Heating capacity / coeff.of perform.

at B-5 / W55

1)

kW / ---

5)

37,5 / 2,4

59,8 / 2,3

76,2 / 2,5

kW / ---

6)

15,0 / 2,1

30,1 / 2,2

33,6 / 2,4

at B0 / W50

1)

kW / ---

5)

43,8 / 3,0

69,8 / 2,9

87,9 / 3,1

kW / ---

6)

18,5 / 2,5

33,3 / 2,8

39,1 / 2,8

at B0 / W35

1)

kW / ---

5)

46,7 / 4,5

75,2 / 4,4

96,3 / 4,6

kW / ---

6)

23,0 / 4,4

37,6 / 4,3

48,4 / 4,6

3.4

Sound power level

dB(A)

65

69

71

3.5

Sound pressure level at a distance of 1 m

dB(A)

50

54

55

3.6

Heating water flow rate at internal pressure difference

m³/h / Pa

4,5 / 2000

6,5 / 2500

8,5 / 3600

3.7

Brine flow rate at internal pressure difference (heat source)

m³/h / Pa

12,8 / 15700

20,5 / 17800

24,0 / 18600

3.8

Refrigerant; total charge weight

Type / kg

R404A / 8,6

R404A / 12,6

R404A / 20,5

4

DIMENSIONS; CONNECTIONS AND WEIGHT

4.1

Equipment dimensions without connections 4)

H x W x L mm

1890 x 1350 x 750

1890 x 1350 x 750

1890 x 1350 x 750

4.2

Equipment connections for heating system

inches

G 1 1/2'' i/ext.

G 2'' i/ext.

G 2'' i/ext.

4.3

Equipment connections for heat source

inches

G 2 1/2'' i/ext.

G 2 1/2'' i/ext.

G 3'' i/ext.

4.4

Weight of transport unit(s) incl. packaging

kg

486

571

652

5

ELECTRICAL CONNECTION

5.1

Nominal voltage; fusing

V / A

400 / 50

400 / 63

400 / 80

5.2

Nominal power consumption

1)

B0 W35

kW

10,45

16,95

20,93

5.3

Starting current with soft starter

A

56

105

120

5.4

Nominal current B0 W35 / cosϕ

5)

A / ---

18,9 / 0,8

30,58 / 0,8

37,8 / 0,8

6

COMPLIES WITH EUROPEAN SAFETY REGULATIONS

3)

3)

3)

7

OTHER DESIGN CHARACTERISTICS

7.1

Water inside equipment protected against freezing

2)

yes

yes

yes

7.2

Performance settings

2

2

2

7.3

Controller internal / external

internal

internal

internal

1)

2)

The heating circulating pump and the controller of the heat pump must be on standby at all times.

3)

See EC Declaration of Conformity

4)

Please keep in mind that additional space is required for pipe connections, operation and maintenance.

5)

2-compressor operation

6)

1-compressor operation

Subject to technical modifications

Issued: 02.11.2005

These data characterize the size and performance capability of the system. For economic and energetic reasons, additional factors such as balance point and control need to be

taken into consideration. Abbreviations have the following meaning, e.g. B10 / W55: heat source temperature 10 °C and heating water supply temperature 55 °C.