Fault

Possible cause

Check

Remedial measures

The unit is running
with reduced or
without cooling or
heating output

Filter is dirty / air inlet / outlet
opening is blocked by by debris

Have the filters been cleaned?

Clean the filters

Doors and windows open /
heating or cooling load was
increased

Have there been any
constructional / application-
related changes?

Close doors and windows /
install additional systems

Neither cooling nor heating
mode has been set

Does the "cooling / heating"
symbol appear in the display?

Correct the settings for the unit

Fins of outdoor unit are blocked
by debris

Is the fan on the outdoor
unit running are the fins
unobstructed?

Check fan or winter regulation,
reduce air resistance

Leaking refrigerant circuit

Are there signs of frost on the
fins of the indoor unit?

Repair by a specialist

Condensation
output on the unit

Drain pipe of the collection
container blocked / damaged

Is unobstructed condensation
drainage ensured?

Clean the drainage pipe and
collection container

Faulty external condensation
pump or float

Is the condensation pan full
of water and the pump is not
working?

Call out a specialist to replace the
pump

Condensation has not drained
away and has collected in the
condensation line

Is the condensation line routing
sloped downhill and is it clear?

Route the condensation line in
a downhill slope or clean it if
necessary

Condensation does not drain
off

Are the condensation lines
unblocked and is there a steady fall?
Are the condensation pump and
float switch functioning correctly?

The condensation line must have
a fall. If necessary, clean the pipe.
A faulty condensation pump and
float switch should be replaced.

Leaking refrigerant circuit

Are there signs of severe frost
on the large stop valve?

Repair by certified service centre.

Problem display by blinker code

Display

Cause

Required action

E0

EEPROM error

Switch off the power to device for

1 min.

Contact specialist dealer

E1

Communication error between outdoor unit and indoor unit

Contact specialist dealer

E2

Phase monitoring has responded

Check wiring

E3

Evaporator fan motor speed too low / defective

Contact specialist dealer

E5

Sensor discharge hot gas AT faulty / connection interrupted

Check connection and plug

E6

Sensor recirculated air IT faulty / connection interrupted

Check connection and plug

P0

Rotational speed monitoring on compressor has responded

(Inverter module)

Check connections CN4, CN1 on the AT

PCB / contact specialist dealer

P1

Overvoltage protection AT tripped (250V)

Check the voltage of the mains cable

P2

Excessive temperature (Klixon) compressor has tripped

Check refrigerant

Check the resistance of the compressor

sensor (normal 0

Ω)

P3

Overcurrent compressor has responded

Check winding resistance of the com-

pressor (1

Ω = U-V / U-W / V-W)

REMKO MXW

18