115 vac models – DoorKing 6500 User Manual

Page 17

background image

15

Chassis

Ground

Electrical Box

Knock-outs

Conduit

Neutral

115 V

A

C

115 VAC Models

Electrical Box

Knock-outs

Conduit

230/460 V

A

C

230/460 V

A

C

115 V

AC Neu

115 V

AC Neu

115 V

AC Hot

2.1 High Voltage Wire Runs

2.2 High Voltage Terminal Connections

The distance shown in the chart is measured in Feet from the operator to the power source. If power wiring is greater than
the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a
separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire
run calculations are based on a 110 VAC power source with a 3% voltage drop on the power line, plus an additional 10%
reduction in distance to allow for other losses in the system.

Route incoming high voltage

power through conduit and into
the operator as shown.

Be sure wiring is installed in

accordance with local codes. Be
sure to color code all wiring.

It is recommended that a surge

suppressor be installed on the
high voltage power lines to help
protect the operator and circuit
board from surges and power
fluctuations.

Secondary operator in a dual

operator application gets power
through the 8-wire connector that
links the 2 operators together. See
2.7 Primary/Secondary (dual) gate
connection.

230 VAC/460 VAC Models

Chassis

Ground

DANGER

HIGH VOLTAGE!

DANGER

HIGH VOLTAGE!

Never run high voltage and low voltage wires in the same conduit. Keep them in separate conduits.

This table illustrates the high voltage wire size and distance requirements.

Reduce the wire distance in half for primary/secondary dual gate applications

Model

Type

Voltage

Required

Amps

Required

Wire Size / Distance in Feet

115

5.4

170

275

460

685

12 AWG

10 AWG

8 AWG

6 AWG

6500 1/2 HP

230

2.7

685

1,100

1,830

2750

6500 1/2 HP

460

1.35

2,875

4,600

7665

11,500

6500 1/2 HP

115

9.7

100

170

280

520

6500 1 HP

230

4.9

380

650

1,100

1,600

6500 1 HP

460

2.5

1,500

2,500

4,000

6,500

6500 1 HP

DO NOT cycle the operator without the OPEN and CLOSE limit sensors in their specific open
and close positions.

The limit sensors or the AC power switch are the only ways to stop the operator once

an open cycle has started. This could cause damage to the gate and/or operator if the gate opens too far!

For 230 and 460
Volt 3-phase
input, use only
two legs of the
incoming 3-phase
power.

6500-065-K-7-08