Dodge SP600 Series User Manual

Page 2

background image

• Ramp Control

- 2 accel/decel rates

- Frequency avoidance bands (3)

to lock out mechanical resonance

points.

- “S” curve acceleration and

deceleration for smooth speed

transitions

• Time Stamped Fault Log

- User Interlock Open

- High DC Bus Voltage

- Low DC Bus Voltage

- Over-Current

- Over-Frequency

- Over-Temperature

- Electronic Motor Overload

- Ground Fault

- Others

• Option Kits

- Braking resistors

- Remote NEMA 4 operator

interface

- PC based V*S Utilities

- EMC line filters

- Network communications modules

- ControlNet

- DeviceNet

- Profibus

- Others

• Stopping Modes

- DB Braking

- Ramp Stop

- Coast Stop

- DC Injection Braking

• Operator Interface Modules

- Multi-line, 6-language graphical

LCD OIM for local or remote

operation. Allows drive control,

configuration, monitoring and

diagnostics. Function keys are

configurable for desired functions.

• Drive Protection

- Line-to-line and line-toground and

output short circuit protection.

Instruction Manuals

• D2-3485

(6SP Series - Frames A, B, C, D)

• D2-3501

(6SB Series - Frames 2, 3, 4, 5, 6)

Service Conditions

• Elevation to 3300 ft.

(1000 meters); Derate 3% for every

1000 ft. above 3300 ft.

• Operating temperature ranges:

- NEMA enclosures:

- 0°C to 40°C (external ambient)

- IP20 enclosures:

- 0°C to 50°C

(50 HP - 45°C; 200 HP - 40°C)

(panel ambient)

• Atmosphere non-condensing relative

humidity: 5% to 95%

• AC line voltage variation: rated input

voltage ±10%

• AC line frequency variation (50/60

Hz): 48 - 62 Hz

• Storage temperature:

- - 40°C to 65°C

(-40°F to 149°F)

Application Data

• Pulse width modulation (PWM)

sensorless vector control

• Maximum load:

- 110% continuous for one minute

(Normal Duty Rating)

- 150% continous for one minute

(Heavy Duty Rating)

• Frequency stability long term: 0.01%

of base speed with digital keypad

0.5% of base speed with analog

speed reference.

• Linearity (speed reference to output

frequency): ± 1.0%

Quiet Motor Operation Up

to 200 Feet

• The SP600 controller uses IGBT

transistors switched at frequencies up

to 10kHz to reduce PWM induced

motor audible noise.

• Unique transistor control circuits also

allow drive to motor distances of

up to 300 feet when applied with

Reliance motors before output filtering

considerations must be applied.

• Tested to ensure that the waveform at

the motor conduit box will not exceed

the limits specified in NEMA MG1

31.40.4.2. at lead lengths of 200 ft.