Duct Mounted E-BUS CO
2
Sensor Technical Guide
Technical Guide
6
Figure 3: Duct Mounted E-BUS CO
2
Sensor & Digital Room Sensor Wiring for VCB-X Controller
Duct Mounted E-BUS CO
2
Sensor Wiring to VCB-X Controller
Duct Mounted E-BUS CO
2
Sensor
The OE256-07 Duct Mounted E-BUS CO
2
Sensor with Remote Pickup
Tube is used for sensing the current CO
2
level in the HVAC unit’s return
air stream. This is useful when you want an average CO
2
reading in the
area served by the HVAC unit or when you don’t want a wall mounted
E-BUS CO
2
Sensor due to sensor tampering concerns in the space.
The OE256-07 Duct Mounted Return Air CO
2
Sensor is comprised of
the CO
2
Sensor, the WattMaster Aspiration Box Assembly, and a Remote
Pickup Tube. See the dimensional and installation information in Figures
2 & 3 for mounting, wiring, and installation details.
The Duct Mounted Return Air E-BUS CO
2
Sensor with Remote Pickup
Tube is designed to be mounted in the return air duct of the HVAC unit
and uses its integral aspiration box to sample the CO
2
level in the duct.
See Figure 3 below for wiring and installation details.
NOTE:
If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
OE256-07 Duct Mounted
E-BUS CO Sensor
2
Note:
1.) The Duct Mounted E-BUS CO Sensor
Connects To The
Controller Using An
EBC E-BUS Cable Of The Required Length
Or The Provided 10 Foot EBC Cable.
2
VCB-X
VCB-X Controller
MADE IN USA
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
www.aaon.com
www.orioncontrols.com
VCB-X CONTROLLER
Orion No.:OE335-23-VCBX-A
AAON No.:
V04740
ANALOG INPUTS
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
BI1
BI2
BI3
Bi4
AO1
AO2
AO3
TR1
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= DCT (DIGITAL COMP. DISCHARGE TEMPERATURE SENSOR)
= SPACE TEMPERATURE SLIDE OFFSET
= EMERGENCY SHUTDOWN
= PROOF OF FLOW
= DIRTY FILTER
= COIL TEMPERATURE SWITCH
= FAN VFD
= ECONOMIZER
= MOD. HEATING
= DIGITAL COMP.
UNLOADER
(24 VAC & UNLOAD
TERMINALS)
BINARY INPUTS
G OUTPUTS
TRIAC OUTPUT
ANALO
STATUS LED BLINK CODES
LED NAME
STATUS1 STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MISSING EXP MODULE
4
2
CO2 SENSOR FAIL
6
2
AIRFLOW SENSOR FAIL
7
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP HI ALARM
3
4
CONT. TEMP LO ALARM
4
4
HIGH HEAD PRESSURE
5
4
WATER PROOF FAILURE
6
4
SUCTION PRESSURE ALARM
7
4
LOW LEAVING WATER TEMP
8
4
WattMaster Label
#LB102093-01-A
Rev.: 1B
E-BUS
EXPANSION
E-BUS
EXPANSION
+24
VAC
GND
ALERT LED BLINK CODES BLINKS
NORMAL OPERATION
0
MISSING OR SHORTED
DISCHARGE TEMP. SENSOR
1
IN 30 MIN. CUTOFF PERIOD
3
IN HIGH TEMP. CUTOFF
4
COMPRESSOR LOCKED OUT
6
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY
COMMON
10 Foot EBC
E-BUS Cable
(Provided)
EBC E-BUS
Cable
with Jack
Connection
37X04
1.2
1.6
4 3 2 1