Wall mounted e-bus co, Sensor, Wall mounted space co – Orion System OE256-05 Wall Mounted v.1 User Manual
Page 4: Sensor wiring to vcb-x controller, Technical guide 4, Wall mounting, Wiring to the vcb-x controller, Figure 2: wall mounted space e-bus co, Optional mounting plate, Ebc e-bus cable

WALL MOUNTED E-BUS CO
2
SENSOR
Technical Guide
4
Figure 2: Wall Mounted Space E-BUS CO
2
Sensor & Digital Room Sensor Wiring for VCB-X Controller
OE256-05
Wall Mounted E-BUS
CO Sensor
2
EBC E-BUS Cable
EBC E-BUS Cable
Display
Override
OVERRIDE
ALARM
NOTE: Mount Both
Sensors At Least
5 Feet Above Floor.
The Digital Room
Sensor Connects To
The
Sensor.
CO
2
OE217-02, OE217-03, OE217-04
E-BUS Digital Room Sensor
VCB-X Controller
MADE IN USA
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY
COMMON
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
www.aaon.com
www.orioncontrols.com
VCX CONTROLLER
Orion No.:OE335-23-VCX
ANALOG INPUTS
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
BI1
BI2
BI3
B4
AO1
AO2
AO3
TR1
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= DCT (DIGITAL COMP. DISCHARGE TEMPERATURE SENSOR)
= SPACE TEMPERATURE SLIDE OFFSET
= EMERGENCY SHUTDOWN
= PROOF OF FLOW
= DIRTY FILTER
= REMOTE OCCUPIED OR COIL TEMPERATURE SWITCH
= FAN VFD
= ECONOMIZER
= SCR OR MODULATING HW HEATING
= DIGITAL COMP. UNLOADER (24 VAC & UNLOAD TERMINALS)
BINARY INPUTS
ANALOG OUTPUTS
TRIAC OUTPUT
I
LED BLINK CODES
LED NAME
STATUS1 STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
OUTPUT FORCE ACTIVE
0
6
WattMaster Label
#LB102093-01-A
Rev.: 1C
E-BUS
EXPANSION
E-BUS
EXPANSION
24 VAC
INPUT
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
www.aaon.com
www.orioncontrols.com
VCB-X CONTROLLER
Orion No.:OE335-23-VCBX-A
AAON No.:
V04740
ANALOG INPUTS
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
BI1
BI2
BI3
Bi4
AO1
AO2
AO3
TR1
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= DCT (DIGITAL COMP. DISCHARGE TEMPERATURE SENSOR)
= SPACE TEMPERATURE SLIDE OFFSET
= EMERGENCY SHUTDOWN
= PROOF OF FLOW
= DIRTY FILTER
= COIL TEMPERATURE SWITCH
= FAN VFD
= ECONOMIZER
= SCR OR MODULATING HW HEATING
= DIGITAL COMP. UNLOADER
(24 VAC & UNLOAD TERMINALS)
BINARY INPUTS
G OUTPUTS
TRIAC OUTPUT
ANALO
STATUS LED BLINK CODES
LED NAME
STATUS1 STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
AIRFLOW SENSOR FAIL
7
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
OUTPUT FORCE ACTIVE
0
6
WattMaster Label
#LB102093-01-A
Rev.: 1A
E-BUS
EXPANSION
E-BUS
EXPANSION
+24
VAC
GN
D
ALERT LED BLINK CODES BLINKS
NORMAL OPERATION
0
MISSING OR SHORTED
DISCHARGE TEMP. SENSOR
1
IN 30 MIN. CUTOFF PERIOD
3
IN HIGH TEMP. CUTOFF
4
COMPRESSOR LOCKED OUT
6
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY
COMMON
Wall Mounted Space CO
2
Sensor Wiring to VCB-X Controller
Wall Mounting
The OE256-05 Wall Mounted E-BUS CO
2
Sensor utilizes a sub-base
mounting plate with a modular phone jack providing quick and easy
mounting and wiring. The wall-mounted sensor’s sub-base is compat-
ible with standard junction boxes. A locking screw secures the assembly
to the wall.
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that
can be used, if necessary, to cover the sensor sheet rock opening.
This mounting plate screws onto the back of the housing base.
The mounting plate is then mounted and covers the recessed space
in the wall. A locking screw secures the sensor to the wall. See
Figure 6, page 7 for dimensions.
Wiring to the VCB-X Controller
The OE256-05 Wall Mounted E-BUS CO
2
Sensor connects to the
VCB-X or VCC-X Controller with an EBC E-BUS expansion cable. It
can be daisy-chained
with the Digital Room Sensor (OE217-02, OE217-
03, OE217-04) for applications requiring both a space CO
2
sensor and
space temperature sensor.
Refer to Figure 2 for instructions (VCB-X
Controller shown).