Troubleshooting
Table 1: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
Temperature – Resis-
tance –for Type III 10K
Ohm Thermistor Sensors
Temp
(ºF)
Resistance
(Ohms)
-10
93333
-5
80531
0
69822
5
60552
10
52500
15
45902
20
40147
25
35165
30
30805
35
27140
40
23874
45
21094
50
18655
52
17799
54
16956
56
16164
58
15385
60
14681
62
14014
64
13382
66
12758
68
12191
69
11906
70
11652
Temperature – Resis-
tance – for Type III 10K
Ohm Thermistor Sensors
Temp
(ºF)
Resistance
(Ohms)
71
11379
72
11136
73
10878
74
10625
75
10398
76
10158
78
9711
80
9302
82
8893
84
8514
86
8153
88
7805
90
7472
95
6716
100
6047
105
5453
110
4923
115
4449
120
4030
125
3656
130
3317
135
3015
140
2743
145
2502
150
2288