Technical Guide

CO

2

SENSOR

9

Figure 6: LED ON/OFF Button and Board LEDs

Figure 7: CO

2

Sensor’s Front LED

TB1 Terminal Block (CO

2

Reading)

The TB1 terminal block should only be used to test the sensor when the
sensor cable is plugged into the controller and the sensor and controller
are powered up. Directions: Set the meter for DC volts and connect
the GND probe to the GND terminal and the + probe to the CO

2

0-5

terminal. Look at the output voltage and record it. Multiply the voltage
times 400. The value should match the CO

2

as read on the System Man-

ager TS, Modular System Manager, Modular Service Tool, or Prism. If
the signal doesn’t match the sensor reading, call WattMaster Controls
for a replacement.