CO

2

SENSOR

Technical Guide

4

Figure 2: Wall Mounted Space CO

2

Sensor & Digital Room Sensor Wiring for VCM-X E-BUS Controller

OE217-00 or OE217-01

Digital Room Sensor

OE256-01

Wall Mounted Space

CO Sensor

2

OE332-23E-VCMX

VCM-X E-BUS Controller

TSDRSC Cable

TSDRSC Cable

Display

Override

OVERRIDE

ALARM

NOTE: If The

Sensor Is Used

With The Digital Room Sensor, The
CO Sensor Always Connects To The
VCM-X Or RNE Controller First Using
A TSDRSC Cable Of The Required
Length. The Digital Room Sensor
Then Connects To The CO Sensor
With Another TSDRSC Cable.

CO

2

2

2

The

Total Length Of Cable For Either One
Or Both Sensor Cables Combined
Cannot Exceed 160 Feet.

GND

TMP

Space Temperature Sensor

hown

OE210, OE211, OE212, OE213

(OE213 S

)

OVR

R

E

L

O

C

R

E

M

R

O

A

W

AUX

Wire Required For

Sensors With Slide

Adjust Option Only

Set Jumper For

THERM When Space

Sensor Slide

Adjust Is Wired To AI7

NOTE: A Space Temperature Sensor Can Be
Used Instead Of the Digital Room Sensor. Either
The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply Air
Temperature Reset Signal Option (By Others) May
Be Connected To An AI7 On The VCM-X Or RNE
Controller. Only One Option Is Allowed, Not Both.

AI1

AI7

GND

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

VCM-X E-BUS Controller

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label

#LB102033-01

OE332-23-VCMX-A VCM-X CONTROLLER

WA
RN
IN

G

OBSERVE

POLARITY

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label
#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1 STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

Wall Mounted Space CO

2

Sensor Wiring to HVAC Unit Controller

Wall Mounting

The OE256-01 Wall Mounted Space CO

2

Sensor utilizes a sub-base

mounting plate with a modular phone jack providing quick and easy
mounting and wiring. The wall-mounted sensor’s sub-base is compat-
ible with standard junction boxes. A locking screw secures the assembly
to the wall.

Optional Mounting Plate

Included with the Digital Room Sensor is a mounting plate that
can be used, if necessary, to cover the sensor sheet rock opening.
This mounting plate screws onto the back of the housing base.
The mounting plate is then mounted and covers the recessed space
in the wall. A locking screw secures the sensor to the wall. See
Figure 8, page 10 for dimensions.

Wiring to the HVAC Unit Controller

The OE256-01 Wall Mounted Space CO

2

Sensor connects to the VCM-X

E-BUS or RNE Controller with the TSDRSC modular cable. It can be
daisy-chained

with the Digital Room Sensor (OE217-00 or OE217-01)

or used separately from a Space Temperature Sensor (OE210, OE211,
OE212, or OE213) for applications requiring both a room CO

2

sensor

and room temperature sensor.

Refer to Figure 2 for instructions (VCM-X

E-BUS Controller shown).