beautypg.com

Dell J730N User Manual

Page 20

background image

18

|

Installation and Startup

Hardwiring the UPS Input

WARNING:

Only qualified service personnel (such as a licensed electrician) shall perform the electrical

installation. Risk of electrical shock.

The Dell Online Rack hardwired models require a dedicated branch circuit that meets the following

requirements:

S

250V/30A, 2-pole circuit breaker (25A for 3750W/230V UPS models) to provide short circuit and

overcurrent protection

S

The protection device requires a two-pole disconnection device between the UPS output and the

load (see Figure 6)

S

The breaker must be wall-mounted and be readily accessible to the operator

S

For Europe, the breaker must meet the IEC/EN 60934 standard and have a contact air gap of at

least 3 mm

S

200–240 Vac

S

Single-phase (4200W/208V model is split-phase)

S

50/60 Hz

S

Flexible metal conduit (recommended for ease of service and maintenance)

AC Mains

Wall

2-pole

Breaker

UPS

Line

Neutral

Figure 6. Circuit Breaker Diagram

This manual is related to the following products: