offset point type desc
------- ------- ------- ------------------
118 40119 UINT16 RF BadChecksum packets
119 40120 UINT16 RS485 BadChecksum packets
120 40121 UINT16 RF RX Good packets
121 40122 UINT16 RS485 RX Good packets
122 40123 UINT16 RF TX packets
123 40124 UINT16 RS485 T Good packets
124 40125 UINT16 RF TX resend packets
125 40126 UINT16 RS485 TX resend packets
126 40127 UINT16 RF RouteChange packets
127 40128 UINT16 RS485 RouteChange packets
128 40129 UINT16 Number of known nodes. (including ourselves)
129 40130 UINT16 Our modbus address
130 40131 UINT16 R9120 Hardware Version (0=rev-A, 1=rev-B, etc)
131 40132 UINT16 Model number bytes 1,2 (4 registers = 8 char string)
132 40133 UINT16 Model number bytes 3,4 (4 registers = 8 char string)
133 40134 UINT16 Model number bytes 5,6 (4 registers = 8 char string)
134 40135 UINT16 Model number bytes 7,8 (4 registers = 8 char string)
135 40136 UINT16 Radio Serial MSW
136 40137 UINT16 Radio Serial LSW
137 40138 UINT16 Radio Firmware
138 40139 UINT16 Radio Type 1=R9120-1(lowpower), 2=R9120-3(highpower)
0=unknown)
139 40140 UINT16 (R/W) Modbus 485 timeout in ms. Default 240ms range 40max
to 2000ms. Affects modhopper in master mode only.
(max 5000ms in v1.17)
140 40141 UINT16 (R/W) Pulse KYZ flag bitmap. 0x01 = pulse1 kyz mode,
0x02 = p2, etc.
141 40142 UINT16 Reserved
142 40143 UINT16 (R/W) RS485 force master/slave modes. 0=auto/default,
1=force-master, 2=force-slave. (firmware 1.17 or later)
143 40144 UINT16 RS485 master/slave mode status. 0=master, 1=slave.
(firmware 1.17 or later)
144 40145 UINT16 RS485 baud rate. 2=9600, 3=19200. (firmware 1.17 or
later)
145 40146 UINT16 (R/W) contact closure threshold. in ohms. 100-2550 ohms
allowed. (rev-c only, firmware 2.02 or later)
146 40147 UINT16 (R/W) contact closure speed, pulse speed: 0=10Hz/default,
1=50Hz, 2=100Hz, 3=250Hz (firmware 2.02 or later)
147 40148 UINT16 power supply voltage monitor (rev-c only) scale: x100
148 40149 UINT16 pcb temperature monitor (rev-c only) scale: x100
149 40150 UINT16 400MHz RX Good packet count (rev-c only)
150 40151 UINT16 400MHz RX Bad packet count (rev-c only)
151 40152 UINT16 (R/W) minimum packet time, how frequent to save sensor data
packets. (10-2550 seconds) (firmware 2.02 or later)
152 40153 UINT16 RS485 serial port option:(firmware 2.05 or later)
bits 0-1: 0=N, 1=E, 2=O
bit 2: 0=8bit, 1=7bit
bit 3: 0=1stop, 1=2stop
Note: read only, always returns 8N1
Page 13
ModHopper R9120 rev C – Wireless Modbus/pulse transceiver