Nortec OnLine GSTC User Manual
Page 12
8 | Installation
Table 2: Status Screen Variables - CONTINUED
Variable Name
Displayed Information
Description
Product LIne
GSTC
SETC
Service Indicator
On/Off Lamp
Indicator
Provides current service status. The yellow
service light is lit when service is due.
X
X
Software Version
Numerical Chart Item
Indicates the software version installed on the
Humidifiers mainboard.
X
X
Steam Production
On/Off Animated
Indicates that the humidifier is producing steam
in response to a demand signal.
X
X
System Demand
Correct Output
0-100% Numerical Data
Displays the humidifier's current demand
output
X
X
Unit Address
Mailing Address Chart
Item
Provides details on the Humidifier's location.
X
X
Unit Model
Unit Identifier Chart Item
Indicates the model type & size of the selected
humidifier.
X
X
Unit Status
On/Off Lamp
Indicator
Indicates if unit has responded to a demand
signal. The green LED is on when a demand
signal is present.
X
X
Water Level High
On/Off Lamp
Indicator
Yellow light is on if water is at a high level. Light
combinations are possible for mid-state water
levels.
X
X
Water Level Mid-
Range
On/Off Lamp Indicator
Green light is on if water is at optimal level.
Light combinations are possible for mid-state
water levels
X
X
Water Level Low
On/Off Lamp Indicator
Red light is on if water is at a low level. Light
combinations are possible for mid-state water
levels.
X
X
Weighted Hours
Hours Chart Item
Equivalent operating hours convoluted to 100%
steam production. Ex. Weighted hours = 2
hours at 50% demand.
X
X
Manual Drain
On/Off Chart Item
Drain unit when “on”.
X
X
Pre-Clean
On/Off Chart Item
Initiates a pre-clean cycle.
X
X
Power Reset
On/Off Chart Item
Performs a software reset similar to turning the
unit off and then on again.
0: Standalone unit (default setting)
1: Unit is Master
X
X
Multimode
Status Item
2: Unit is Slave
Lists current signal type the unit is configured
for
0: 0-5Vdc
1: 1-5Vdc
2: 0-10Vdc
3: 2-10Vdc
4: 0-16Vdc
5: 3.2-16Vdc
6: 0-10mA
X
X