beautypg.com

Zero span control signal adjustment (-zs option), Dodge engineering & controls, inc, Installation – Dodge ES142 User Manual

Page 8: Es142 spring return electronic actuators

background image


Dodge Engineering & Controls, Inc.

Toll Free (877) 334-2875 Fax: (978) 244-1422

Installation

ES142 Spring Return Electronic Actuators

129-270 EAI/ES-8 DEI,

Inc.

Zero Span Control Signal Adjustment (-ZS option)


The offset (start point) and
span of the control signal
can be adjusted. The offset,
U0, can be adjusted between
0 to 5 VDC. The span,

∆U,

can be adjusted between 2
to 30 VDC.

100

0

U

O

Δ

U (max. 30 V)

Y

U

(v)

Y

S

(%)

EA041

1R1

2

5

10

35

2)

1)

3)

Ys

Mechanical positioning range

(100% = angle of rotation 90°)

Yu Control

signal

U0

Offset (start point)

∆U Span


Examples above:

Ex. 1. U0 = 0V,

∆U = 2V

The minimum working
range for Ys = 100%.

Ex. 2. U0 = 5V,

∆U = 30V

The maximum working
range for Ys = 100%

Ex. 3. U0 = 0V,

∆U = 10V

Factory setting

Offset, Uo

2

4

0

1

3

5

Span, U

30

2

15

10

5

20

25

Control
Signals

Uo

U

EA0287R1

Figure 14. The Minimum and Maximum Control Signal

Adjustment.

Figure 15. Setting for

10V Span, 0 Offset.

Example:

Open the actuator from 0% to 50% (45°) using a control signal of Umin = 2V to Umax = 10V.
Calculating the value of

∆U:

V

16

50

2)

(10

x

100

%

in

rotation

of

angle

Working

min)

U

max

(U

%]

[

100

U

=

=

=

Δ

Settings:
Offset U0 = 2, Span:

∆U = 16V

Umin = minimum control signal
Umax = maximum control signal

100

0

Δ

U (16 V)

Y

U

(v)

Y

S

(%)

2

18

10

U

min

U

max

50

U

o

EA0412R1