beautypg.com

Appendix a – Drolet ECO-35 User Manual

Page 28

background image

28

APPENDIX A


HORIZONTAL AND VERTICAL VENT CHART



Let’s imagine an installation consisting of a horizontal vent coming out at the back of the stove on a total distance of 8 feet.
This horizontal run is followed by a Tee and a 6-foot vertical rise. This type installation is not acceptable. As you can see,
the vent termination is clearly outside the allowed configuration zone on the chart. The venting system does not have at
least one foot of vertical rise for each foot of horizontal run.

Instead, if the installation consisted of a horizontal vent coming out at the back of the stove on a total distance of 4 feet,
followed by a Tee and a 6-foot vertical rise, it would be acceptable. The installation would end be within the allowable
configuration zone on the chart since it would have at least one foot of vertical rise for each foot of horizontal run.
Furthermore, the total vertical rise would be at least 3-foot high.







Possible Vertical
vent length (feet)

Possible Horizontal
vent length (feet)

If you plot your venting
system configuration on
this chart, your wall or
roof termination should be
within the grid.