III. ADJUSTING OF THE LOAD MANAGER 2

The factory adjustment for the Load Manager 2 is for the first relay to be energized. The 2nd relay

is energized at a voltage .5 volts lower than relay 1. No separate adjustment is provided for relay 2.

To readjust the setpoint, remove the 4 screws and lift off the cover. Connect a variable voltage source

to the battery input terminals and an ohmeter across the normally open contacts of relay 1. Vary

the input voltage to the point at which relay 1 just becomes energized. Turn the trimmer resistor

R100 slightly CCW to lower the setpoint or slightly CW to raise the setpoint. Check the new setting

to determine what voltage will cause the relay to be energized.

IV. FIGURE 2, VOLTAGE ADJUSTMENT

170 Cherry Avenue

West Sayville, NY 11796

www.kussmaul.com

Ph: 800-346-0857

Fax: 631-567-5826

[email protected]

4

CAUTION

The circuit responds very slowly so allow ample time, 15 to 30 seconds for the

circuit to respond to voltage changes. This time delay is required to prevent the

relay from chattering for small changes in voltage around the setpoint.