beautypg.com

Installation, Introduction – Kussmaul Electronics 091-80-12 User Manual

Page 2

background image

INSTALLATION

The Auto Charge T Automatic Battery Charger should be installed in an area with adequate

ventilation. A power cord is supplied for connection to 115 volts 60 Hz.

1. Mount the charger using the four holes provided for this.

2. Connect the wiring from the battery to the Output Terminal Strip. Spade lugs that

have been securely crimped, or soldered, should be used.

3. Double check all wiring before proceeding.

4. Wire the A.C. power line cord to 115 volts.

5. Pilot light will light to show that the charger has power.

The Auto Charge T, Model 091-80-xx battery charger is a compact completely automatic

charger designed for installation in systems which require a transient suppressed

charger. Ideal for electric utility applications to maintain the batteries used in high

voltage circuit breaker trip circuits or wherever the charger may be exposed to high

electromagnetic fields. Red, yellow and green indicators are provided to indicate

whether the battery is fully charged, charging normally or receiving the maximum current.

Construction of the Auto Charge T is extremely rugged to withstand shock and vibration.

In addition the line power input lines and the charger output terminals are provided with

filters and MOV transient suppressors. These suppression circuits permit the charger to

meet ANSI/IEEE C37.90.1-1989.

INTRODUCTION