Kussmaul Electronics 091-45 User Manual

Page 2

background image

Switch #1 Switch #2 Switch #3 Trips Below:

OFF

OFF

OFF

13.01 Volts

OFF

OFF

ON

12.76 Volts

OFF

ON

OFF

12.52 Volts

OFF

ON

ON

12.29 Volts

ON

OFF

OFF

12.07 Volts

ON

OFF

ON

11.85 Volts

ON

ON

OFF

11.64 Volts

ON

ON

ON

11.44 Volts

INTRODUCTION

The UV-OV Relay is a device which continuously monitors the voltage of a battery system and
detects overvoltage and undervoltage conditions. A set of contacts are provided for each of
these conditions. The values of the overvoltage and undervoltage detection points are easily
and independently programmable by accessible “DIP” switches behind the removable cover.
An adjustable time delay of 8 to 150 seconds is provided.

INSTALLATION
Figure 1 is a view of the programming switches with the snap-on top cover removed. Refer to
this figure when programming the unit.

Programming Switches

FIGURE 1

TEST/RUN

Switch

TEST

Undervoltage
Programming

Switches

Overvoltage

Programming

Switches

R U N

(a) Select the desired undervoltage trip point from the column to the far right in table 1 below.

(b) Set switches #1, #2 and #3 to the settings shown in table 1 corresponding to the
selected trip point in step (a).

TABLE 1 Undervoltage Programming