Herrmidifier Herricane CS User Manual
Page 3
Herricane CS
®
Series
I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
3
www.herrmidifier-hvac.com
I. GENERAL INFORMATION
Warranty
1. Herrmidifier warrants to the buyer or any user during the
duration of the Warranty that the humidifier described
in this manual will be free from defects of material and
workmanship for a period of three (3) years from the
date of shipment.
2. For this Warranty to be effective, this humidifier must
be installed, operated and maintained in accordance
with the Installation Instructions, Operations and
Maintenance Manual(s) supplied with the humidifier.
3. In the event of a defect or malfunction in this product during
the Warranty Period, user may contact the Customer
Service Department or their Herrmidifier Representative
for a Material Return Authorization (MRA) number. Items
tagged (on the outside of the box) with this number may
be returned to Herrmidifier for replacement. Incidental
expenses such as cost of transporting the humidifier
to Herrmidifier or labor associated with removal/
replacement of the parts shall be paid by the user. Upon
completion of the reconditioning, the humidifier will be
returned at no cost to the user. Items returned without
an MRA number will not be accepted!
4. This Warranty does not cover field labor for
repairs to this humidifier or any special, indirect or
consequential damages. Some states do not allow
the exclusion or limitation of incidental or consequential
damages, so the above limitation may not apply to you.
5. If, after a reasonable number of attempts to do so,
Herrmidifier is unable to remedy any defects or
malfunctions in this humidifier, then the user may elect
either a replacement of such product or part which may
be defective without charge or a refund of the buyer’s
original purchase price.
6. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to
state.
NOTE
Water quality plays a vital role in the performance and
maintenance requirement of any humidifier. Adjust-
ments to the circuit board may be necessary based on
the incoming water quality.
Performance problems associated with water quality
are not warranty issues!
Evaporative distance can be measured in two ways.
“Bulk” evaporative distance beyond which condensation
will not occur on objects at duct temperature. “Last
Wisp” evaporation is the point beyond which there is no
visible steam and it is safe to install high-efficiency filters.
Herrmidifier has published evaporative distance tables
for standard conditions (55°F, 70% downstream relative
humidity). Steam intensity and air velocity are evaluated at
these conditions. A second table is published which allows
correction to non-standard )other than 55°F and 70%
relative humidity downstream of the humidifier) conditions.
The tables are only useful with Herricane CS Series
humidifiers. Application to other brands of humidifiers is
not recommended. Differences in distribution patterns will
cause problems!
If you desire, you may forward your design criteria to Herr-
midifier for a written analysis of your evaporative distances.
We will be able to define the “bulk” and “last wisp” evapo-
rative distance based on this criteria only. If any changes
are made to the design, a follow-up analysis must be made
to assure fail-safe operation.