IV. ACCESSORY INSTALLATION
STRAINERS:
The strainers come in a variety of sizes depending on the steam pressure and flow. The inlet and outlet ports should be
mounted in the horizontal position. The exhaust port, located closest to the outlet port should be pointed down to catch debris.
TRAPS:
Supply: Standard supply traps offered by Herrmidifier are Float & Thermostatic Traps (F&T). Their model number will be
determined by the inlet pressure and capacity requirements. There are two inlet ports and two outlet ports for a total of four
possible piping combinations to simplify installation. The inlet ports are the top ports and the outlet ports are the bottom ports.
Inverted buckets are also available upon request.
Manifold: The manifold traps can be F&T’s as described above or thermostatic traps (T&A). The T&A traps are available in
two configurations. The vertical traps have the inlet port in the top and the outlet on the bottom. The angle trap[s have the inlet
on the side and the outlet on the bottom. Thermostatic traps should be located a minimum of 12” away from the distribution
system to allow for adequate cooling of condensate prior to the trap.
TEMPERATURE INTERLOCK SWITCHES:
The design of the CS Series does not require the use of temperature interlock switches for proper operation. The supply trap
will keep the supply line free of condensate and the manifold design allows for rapid heating and the manifold trap can handle
any condensate that is formed. If a temperature interlock switch is desired, it would be installed in the steam line between the
main steam supply line and the supply trap. It would be wired with the control signal to prevent the humidifier from energizing
if condensate is in the system. See figure below.