beautypg.com

Herrmidifier Load Calculator User Manual

Page 14

background image

L o a d C a l c u l a t i o n G u i d e

L o a d C a l c u l a t i o n G u i d e

14

w w w. h e r r m i d i f i e r- h v a c . c o m

Notice that the MAXIMUM HEATING DEMAND LOAD in this

example is 393 lbs./hr. which occurs at 55°F, not at design

outdoor temperature as with traditional heating systems.

Therefore, any humidification system installed to handle this

load will have to have a maximum capacity of 393 lbs./hr.

water output.

Cooling Load

As we have seen, moisture is removed by condensation dur-

ing the cooling process as the air is cooled below its dew

point and then reheats to room temperature. This condensed

moisture must be replaced when its loss causes the R.H. to

fall too low. To determine the maximum demand load due to

cooling observe the following steps:

Step 1. Determine the amount of moisture per cubic foot of

air that will be removed by condensation during the cooling

process as this will have to be replaced. This is done by us-

ing Table 2-A to determine the grains of moisture per cubic

foot of air at indoor design temperature and R.H., then deter-

mining the grains of moisture per cubic foot of air after it has

been cooled and subtracting this figure from that obtained for

the design temperature and R.H.

In determining the amount of moisture in the air after it has

been cooled, it is necessary to know the air temperature

drop across the cooling coils. This is usually a 15°F drop

with standard air conditioning equipment, but can vary from

manufacturer to manufacturer. It is best to check. Further,

the R.H. of the air after cooling will be about 85% rather than

100% because, only that portion of the air in contact with

the cooling coils will be cooled to coil temperature with con-

densation resulting. The coil temperature will be less than

the exit air temperature. The following example will illustrate

Step 1.

Example:

60 tons air conditioning (standard) maintaining 70°F at 65%

R.H.

Moisture content of air at design

70°F, 65% R.H. = 8.10 gr./CF x .65(%) = 5.26 gr./CF

-Moisture-content after cooling

55°F, 85% R.H. = 4.89 gr./CF x .85(%) = 4.15 gr./CF

Moisture removed during cooling= 1.11 gr./CF

Therefore we must replace 1.11 grains of moisture per cubic

foot of air to return the air to the desired condition of 70°F,

65% R.H. after cooling in this example.

Step 2. Determine the volume of air passing over the cool-

ing coils per hour. This is usually about 400 CFM per ton of

rated capacity for standard air conditioning equipment, but

this may vary with the make of equipment. It is always best

to check. Computer room air conditioning equipment is often

designed for 500-800 CFM per ton of rated capacity.

Example:

60 ton air conditioning

60 x 400 CFM = 24,000 x 60 min./hr. = 1,440,000 CFH

Step 3. Since almost all standard air conditioning equipment

is usually slightly overrated to allow it to shut down periodi-

cally and defrost, it is necessary to determine the maximum

“ON” time during any given hour, since this is when mois-

ture is being removed from the air. This is usually 80%, but

should be checked, as special equipment may be designed

to cool rapidly and use less “ON” time.

Step 4. The MAXIMUM COOLING DEMAND LOAD for hu-

midification can now be calculated using the following for-

mula:

gr./CF needed x CFH x “ON” time

7,000 gr/lb. = lbs./water req.

Using the preceding examples in Steps 1-3:

1.11 gr./CF x 1,440,000 CFH x.80 “ON” = 183 lbs.

7,000 gr./lb. water/hr.

In this example, the MAXIMUM COOLING DEMAND LOAD

is 183 lbs. water/hr. Therefore, any humidification system

installed to handle this load will have to have a maximum

capacity of 183 lbs./hr. water output.

Cooling Load- Low Temperature (32°F-47°F)

In special applications, such as cold storage, the cooling

equipment (refrigeration) is usually designed to have an air

temperature drop across the coils of less than 15°F, to move

a greater volume of air across the coils than the 400 CFM per

ton experienced with standard air conditioning equipment

and to have a definite “OFF” cycle for defrosting.