Replace the bushing(s) [10] and/or O-Ring 
seal [67] in the spindle guide sub-assembly. 
Insert the spindle tube and make sure that it 
moves freely. Insert the spindle rod sub-
assembly into the tube and seat the tube 
against the upper cap. Install the lower 
spindle cap [25] and screw the rod into the 
swivel ball on the pallet sub-assembly. Hold 
the support plate [4] and tighten the swivel ball 
[24] securely. 
Place a gasket [20] on the actuator mounting 
surface of the valve body. Turn the lower 
actuator housing [14] with spindle and pallet 
assembly upright. Place two temporary blocks 
between the housing and the diaphragm 
support plate [4]. This will hold the pallet 
suspended above the body seat when it is 
lowered into the body. On small valve sizes, 
the spindle/seat assembly can be supported 
manually. 
Carefully lower the assembly into the body. 
Raise the diaphragm support plate manually 
and remove the wood blocks. Lower the 
diaphragm support plate gently, while aligning 
the diaphragm hole pattern with the body 
studs, until the pallet assembly is seated in 
the valve body. Install the diaphragm [15] 
onto the studs. 
Note: If the Model 1402A pilot is used, a 
spacer gasket [58] is installed between the 
lower actuator housing [14] and the 
diaphragm [15]. The pilot will be connected to 
a hole on the actuator mounting surface of the 
valve body. In this case, the odd hole in the 
body gasket [20], lower actuator housing [14] 
and spacer gasket [58] must align with the 
body hole. 
WARNING
Failure to properly align gaskets and the 
lower housing on valves equipped with the 
Model 1402A pilot will prevent the valve 
from opening. 
2
14
15
58
20
20
Figure 8: 1402A Pilot Connection
Note: If the diaphragm is not attached to the 
support plate, install the diaphragm after the 
pallet assembly is in place. Lay it on top of 
the support plate and align the holes with the 
studs. 
Install the second gasket [20], upper actuator 
housing [2], lock washers [8] and hex nuts [6], 
and tighten evenly in a criss-cross pattern. 
Wrap the threads of the pipe nipple [1] with 
Fluoropolymer tape and thread it into the 
coupling in the upper actuator housing [2]. 
Install the pilot valve [51] and reconnect the 
tubing between the body pickup fitting and the 
pilot inlet port. 