Certification – Groth 7588 User Manual
Page 2
IOM-7588
REV. B 12541
Ref. 97288
2
Table of Contents
Section Page
Introduction 2
Certification 2
Integrated temperature sensors
2
Design & Function
3
Installation 3
Maintenance 4
Model Identification
6
Product Limited Warranty
6
Tables
Bolt torque
4 & 5
MESG
tables
6
Attachments
ATEX Declaration of Conformity
Cert. # IBExU12ATEX2018 X
Drawings SCH-7588-01, SCH-7588-
02, SCH-7588-03
INTRODUCTION
This manual is intended to provide
recommended procedures and practices for
installation, operation and maintenance of the
Groth Model 7588 in line deflagration flame
arrester. Any standard procedures and practices
developed for a specific plant or process should
supersede this manual. Although this manual
cannot cover all possible contingencies,
following these guidelines will provide safe,
reliable detonation flame arrester service.
The arrester shall be treated as a safety device
and must be maintained by a knowledgeable
repair technician. Carefully read and understand
this manual before installing or servicing this
product.
For information not contained in this manual,
please contact:
Groth Corporation
13650 North Promenade Blvd.
Stafford, TX 77477
281-295 6800
281-295-6999 Fax
CERTIFICATION
Groth Model 7588 in line deflagration flame
arresters are manufactured in compliance with
the ATEX Directive 94/4/EC, as confirmed by
Certificate IBExU12ATEX2018 X. This
certification covers the following sizes, materials
and limits for use.
Sizes included are all those shown on drawings
SCH-7588-01, SCH-7588-02, and SCH-7588-
03. Materials included are all materials that
satisfy the strength and pressure ratings
specified on these drawings.
These arresters are suitable for in line
deflagrations and short time burning. Run up
length from source of ignition is:
Connection
Size
(mm)
Run Up
Length/Diameter
p
TB
/ p
O
2”
(50mm)
50 15.7
PSIA
(1.08 Bar)
3”
(80mm)
20 15.7
PSIA
(1.08 Bar)
4””
(100mm)
10 15.7
PSIA
(1.08 Bar)
6”
(150mm)
10 15.7
PSIA
(1.08 Bar)
8”
(200mm)
10 15.7
PSIA
(1.08 Bar)
10”
(250mm)
10 15.7
PSIA
(1.08 Bar)
12”
(300mm)
10 15.7
PSIA
(1.08 Bar)
Explosion Gas Group
IIA1
MESG of vapor mixture
≥ 0.045” [1.14 mm]
Operating Temperature
–4
o
F to 140
o
F [-20
o
C to 60
o
C]