Specifications
Overview
The XP Series products are Power Distribution Units (PDU) intended for connection to a 30 Amp
AC Mains circuit
1
. The PDUs are designed to be powered by either a single phase or a three phase
AC input circuit. Three phase units can be configured for either a delta or wye input connection.
XP Series PDUs can optionally be configured with a Geist Current Meter that provides local
monitoring and display of each output circuit current. Alternatively, XP Series PDUs can be
configured with a Geist Current Monitoring (EM) Meter that provides both local and remote
monitoring of input and output line current. XP Series PDUs can also be configured with advanced
wireless technology from Packet Power which allows for remote monitoring of input and output
power through a wirelessly connected gateway.
Environmental
Temperature
Operating:
10°C (50°F) min
45°C (113°F) max
Storage:
-25°C (-13°F) min 65°C (149°F) max
Humidity
Operating:
5% min
95% max
(non-condensing)
Storage:
5% min
95% max
(non-condensing)
Elevation
Operating:
0 m (0 ft) min
2000 m (6561 ft) max
Storage:
0 m (0 ft) min
15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
NEMA 5-15R or L5-15R
125 Volts, 15 Amp
NEMA 5-20R or L5-20R
125 Volts, 20 Amp
NEMA 6-20R or L6-20R
250 Volts, 20 Amp
IEC-320 C13
125/250 Volt, 15 Amp (per Receptacle Bank)
IEC-320 C19
125/250 Volt, 20 Amp
Networking (For Current Monitoring (EM) Meter Units Only)
Protocols
HTTP, ICMP, DHCP, TCP/IP, FTP
Ethernet Link Speed
1
Global Versions of the XP Series are intended to be connected to a 32 Amp AC Mains Branch
Circuit