beautypg.com

Before installation – Fronius Personal Display DL User Manual

Page 55

background image

53

EN-US

Before installation

Safety

Installation speci-
fications

The Fronius Personal Display DL should only be used indoors due to its IP20 degree of
protection.
The device should be protected against direct exposure to moisture.

The antenna can be set up and operated outdoors without limitation.

Inserting a Fro-
nius Display Card
or Fronius Com
Card into the in-
verter

Insert and secure a Fronius Display Card or Fronius Com Card as per the inverter's
operating instructions.

Follow all safety information.

Attaching the an-
tenna to the wall
and connecting to
the inverter

The antenna included with the Fronius Personal Display Card comes with a 2 m long con-
nection cable. If the inverter is located within a room shielded from radio waves, it is pos-
sible to install the antenna outside of this area.
A cable extension is available from Fronius for Fronius IG 300-500 inverters or Fronius CL
inverters.

The following steps only apply to the following system configurations:

Fronius Personal Display DL
+
Fronius Personal Display Card

WARNING! Operating the device incorrectly can cause serious injury and dam-
age. Do not use the functions described until you have thoroughly read and un-
derstood the following documents:
-

these operating instructions

-

all operating instructions for system components, especially the safety rules

WARNING! An electric shock can be fatal. Danger from grid voltage and DC volt-
age from solar modules.
-

The inverter connection area should only be opened by a licensed electrician
after being disconnected from the grid power.

-

Plug-in cards should only be inserted after the inverter has been disconnect-
ed from the AC and DC sides.

-

Please note the safety information in your inverter's operating instructions.

NOTE! Follow general ESD precautions when handling option cards.

NOTE! When inserting the Fronius Display Card into the Fronius IG, the plug-in
card
-

should only be inserted into slots labeled 'Option 1,' 'Option 2' or 'Option 3'

-

should not be inserted under any circumstances into the slot on the far left
labeled 'ENS'

NOTE! The Fronius Com Card is not required for system configurations with a
Fronius Personal Display DL, Fronius Personal Display DL Box and Fronius IG
TL. The Fronius IG TL comes standard with a com card function.

1