Automax CENTURA™ CE Series FCD AXENIM0037-01 – 12/05
10
Typical Actuator Specifications
Action
Reversible
Range of Adjustability
0° -270°
Supply Voltages
AC:
115 VAC
+/-10%
230 VAC
50/60 Hz
24 VAC
DC:
12 VDC
24 VDC
Temperature Rating
-40°F (-40°C) to 160°F (70°C)
Enclosure Ratings
Nema 4, 4X, 7, 9 Watertight and Explosion-proof
Class I Groups C&D, Div. 1&2
Class II Groups E, F&G, Div. 1&2
Motor Types
AC:
Permanent Split Capacitor, Class B Insulation
DC:
Brush
AC Motor Thermal Protection
Automatically resetting
Travel and Aux. Switches
SPDT, Form C
15 amp 125 VAC 1/2 HP, 10 amp 250 VAC, 1/2 amp 125 VDC
Conduit Connections
3/4-14 NPT
Manual Override
300 In-lbs max input
Corrosion Protection
Chromate conversion undercoat with polyester electrostatic powder top coat
Terminal Strip Hookup
300V, 30 amp, 12-26 AWG
Lubrication
Permanently lubricated
Gear Train
Heat treated alloy steel able to withstand stall torque
Note: The above ratings may change depending on model configurations and options provided. Products may
differ as the result of the Company policy of continuous product improvement.
Motor
option
Motor
Voltage
Duty
Cycle
(1,3)
Run
Current
(amps)
Locked
Rotor
(amps)
Cycle times in Seconds per 90 Degrees
actuator Model
CE2
CE4
CE7
CE1
CE5
Std.
115 AC
25
1.1
1.3
3
5
6
11
18
A
115 AC
Extended: 75
0.5
0.6
6
10
17
24
36
B
12 DC
100
1.6
3.0
(2)
6
9
16
21
32
C
24 DC
100
0.9
2.0
(2)
6
8
15
20
30
D
230 AC
25
0.7
0.8
3
5
6
11
18
F
230 AC
Extended: 75
0.3
0.4
6
10
17
24
36
J
24 AC
100
0.5
0.8
3
5
6
11
18
torque and Weights
Torque (In-Lbs)
250
400
700
1000
1500
Torque (N-M)
28
45
79
113
169
Weight (Lbs)
18
18
18
18
20
Weight (Kg)
8
8
8
8
9
Notes:
1. Duty cycle is the limit of “on” time as percentage of total cycle time. For example, the CE2 with standard motor
runs 3 seconds to open or close the valve. The motor must remain off for 9 seconds prior to starting the close
cycle. DC motors may be operated continuously.
2. Do not lock up DC motors.
3. CE5 duty cycles for AC motors are 20% for standard duty and 70% for extended duty.
. For 180 degree applications, simply multiply the above cycle times by 2.