User Instructions WRG Series Standard Actuator - WCENIM0123-00 12/12

DA Hydraulic Override Pressure for Rated Body torque

Model

WRG3

WRG4

WRG5

WRG6

WRG7

WRG8

MOP, psi

1860

2100

2050

1950

1950

2150

Max. System Pr

2500 psi

Fig.: 3 Install Hydraulic Override (DA)

4.4.2 Remove end cap of the hydraulic cylinder. With a suit-

able socket/tube spanner located on the hex head of the

hydraulic piston end, thread in and tighten the piston rod

into the threading of the Torque Module’s Guide Block.

Torque to values, as for pull rod/ piston rod.

4.4.3 Put back the end cap, taking care not to damage the

cap seal, and tighten fully the tie rod nuts of the hy-

draulic cylinder.

4.4.4 Connect the ports of the hydraulic cylinder to the di-

rection control valve on the hydraulic power pack. Re-

fer schematic.

4.4.5 Check and ensure the Hydraulic pressure setting of

the pump does not exceed the MOP setting, refer table

below. Use the plugged port on the pressure line Tee,

to connect a suitable pressure gage.

4.5 Operation –DA Override

4.5.1 For Manual Override operation, turn the 3 way valves

on the pressure module to vent cylinder ports to at-

mosphere and Close the the hydraulic bypass valve,

HBV (if provided externally). Close the pressure re-

lease valve on the pump. Turn the lever on the 4 way

direction control valve on the power pack, to select

the direction of the actuator rotation and stroke the

hydraulic pump.

4.5.2 To restore Automatic operation, turn HBV to Open

position, turn the vent valves to connect the cylinder

ports to air supply pressure and open the pressure

release valve on the hand pump.

CAUTION! Over thrust by the hydraulic override may
cause actuator damage. Prevent damage and un-
safe working, by adjusting the overload valve on the
pump to limit the hydraulic pressure, as shown in
the table.