Fault:

Defective temperature sensor.

Remedy: Check the measuring voltage across terminals 2 and 3 of NRG 211-1.

If the supply voltage 1 – 4 V check temperature sensor. If temperature
sensor is defective replace level probe.

Level switch NRS 2-5: No function when level falls or rises or when level is
below min. level – only the green LED

OPERATION

of the level switch NRS 2-5 is

illuminated

Fault:

Level probe does not enter the liquid.

Remedy: Measure voltage across C18/A18 of NRS 2-5. Check installation of

NRG 211-1 and measure voltage across terminals 2 and 3. If necessary
change position of installation of the level probe.

Fault:

Defective level switch.

Remedy: Measure voltage across C16/A18 (supply voltage for level probe) on

NRS 2-5. Replace level switch if no voltage can be measured.

Fault:

Defective preamplifier.

Remedy: Measure voltage across C18/A18 of NRS 2-5. Measure supply voltage

across terminals 1 and 3 of NRG 211-1 and measuring voltage across
terminals 2 and 3. If supply voltage = 12 V and no measuring voltage
can be measured, replace preamplifier.

Fault:

Defective temperature sensor.

Remedy: Check the measuring voltage across terminals 2 and 3 of NRG 211-1.

If supply voltage = 1 – 4 V check temperature sensor. If temperature
sensor is defective replace level probe.

The temperature measured by means of the resistance thermometer does not
correspond to the actual installation temperature

Fault:

Defective Pt 1000.

Remedy: Replace level probe.