Annex

Fault finding list

Warning

The terminal strip of the NRS 2-4 / NRS 2-5 is live during operation. This
presents the danger of electric shock.
Cut off power supply before inserting or removing the 19" slide-in unit and
before undertaking any installation or maintenance work.

Green LED

OPERATION

at level switch NRS 2-4 / NRS 2-5 is not illuminated

Fault:

The supply voltage has failed.

Remedy: Measure the voltage across A/C28 and A/C30 of the NRS 2-4 / NRS 2-5.

Check power supply and wiring.

No function when level falls or rises – LED

MALFUNCTION

IN

PROBE

and

HIGH

LEVEL

on level switch NRS 2-4 or

LOW

LEVEL

on level switch NRS 2-5

are illuminated

Fault:

The locking screw has not been removed from the level probe NRG 211-1.

Remedy: Remove locking screw.

Fault:

Defective level probe (defective insulating seal, untight stuffing box)

Remedy: Measure voltage across C18/A18 of NRS 2-4 / NRS 2-5. Measure voltage

across terminals 2 and 3 of the NRG 211-1. If voltage

9 V check probe

supply cable and wiring.

No function when level falls or rises – LED

MALFUNCTION

IN

CABLE

on level switch

NRS 2-4 / NRS 2-5 is illuminated

Fault:

Malfunction in probe supply cable (short circuit, interruption).

Remedy: Measure voltage across C18/A18 of NRS 2-4 / NRS 2-5. Measure voltage

across terminals 2 and 3 of level probe NRG 211-1. If voltage

1 V check

probe supply cable and wiring.

Level switch NRS 2-4: No function when level falls or rises or when high level
is exceeded – only the green LED

OPERATION

of the level switch NRS 2-4 is

illuminated

Fault:

Level probe does not enter the liquid.

Remedy: Measure voltage across C18/A18 of NRS 2-4. Check installation of

NRG 211-1 and measure voltage across terminals 2 and 3. If necessary
change position of installation of the level probe.

Fault:

Defective level switch.

Remedy: Measure voltage across C16/A18 (supply voltage for level probe) on

NRS 2-4. Replace level switch if no voltage can be measured.

Fault:

Defective preamplifier.

Remedy: Measure voltage across C18/A18 of NRS 2-4. Measure supply voltage

across terminals 1 and 3 of NRG 211-1 and measuring voltage across
terminals 2 and 3. If supply voltage = 12 V and no measuring voltage can
be measured, replace preamplifier.