Flowserve ZK210 User Manual
Page 9
![background image](https://www.manualsdir.com/files/784644/content/doc009.png)
9
Explanatory Notes
(continued)
Technical Data
Important
For the technical data of the control valve ZK 210, see the name plate.
Valve position
Name plate drawing
Name plate data
Valve lift
1234
50
250
10 LIN
Type with nominal size of body
Gestra serial number
Nominal size of connection [DN]
Rated pressure [bar]
Max. allowable temperature [°C]
1
)
Max. allowable pressure [barg]
1
)
K
vs
value, characteristic curve
1
) If there is no rated pressure stated on the name plate, the maximum allowable pressure
limits are stated together with the associated temperatures.
Example:
°C
300 | 550
barg
250 | 54
The statement of differential pressure corresponds to valve inlet pressure minus valve
outlet pressure.
The scope and layout of the name plate data comply with EN 19.
Pressure/Temperature Rating
Important
In the installation instructions, standard pressure/temperature ratings are
described. For possible deviations, please see the name plate of the control
valve.
Max. allowable pressure
PMA
[barg]
250
217
54
Max. allowable inlet temperature
TMA
[°C]
300
450
550
Max. allowable differential pressure
∆PMX
[bar]
3-stage 100 4/5-stage 180