Malfunctions / troubleshooting, Fault finding list – Flowserve NRGS15-1 User Manual
Page 24

24
Malfunctions / Troubleshooting
Fault finding list
Switchpoint "Pump OFF" exceeded - no function
Fault:
Mains voltage is not applied.
Remedy:
Switch on mains voltage. Connect level switch according to wiring diagram
(Fig. 5).
Fault:
The electrical conductivity is too low.
Remedy:
Set code switch
to 0.5 µS/cm.
Fault:
The earth connection to the vessel is interrupted.
Remedy:
Clean seating surfaces (see Fig. 3) and insert metal joint ring
Ø 33 x 39
DIN 7603 (made from s. s. 1.4301). Do not insulate the level switch with
hemp or PTFE tape!
Fault:
Electronic circuit board defective.
Remedy:
Replace electronic circuit board.
Level below switchpoint "Low level" - no function
Fault:
The electrode tips have earth contact.
Remedy:
Check and, if necessary, change position of installation.
Fault:
If the equipment is installed inside the boiler: The vent hole in the protection
tube does not exist or is obstructed.
Remedy:
Check installation of level switch. Make sure that the level in the protection
tube corresponds to the actual water level (see Examples of Installation).
Switchpoint has been reached - incorrect function
Fault:
The switching function has not been assigned correctly. The electrode tips
have been cut to the wrong length.
Remedy:
Assign the electrode tips correctly and change connections on the electronic
circuit board
correspondingly.
Fault:
The switching function does not correspond to the selected function. The
code switch has been set to the wrong value.
Remedy:
Set code switch
according to the selected function.