Valtek Mark One and Mark Two Control Valves FCD VLENIM001-01-AQ - 8/14

Problem

Probable Cause

Corrective Action

Stem motion

impeded

1. Over-tightened packing

1. Adjust the packing box nuts to slightly over finger-tight

2. Service temperature is beyond

operating limits of trim design

2. Reconfirm service conditions and contact factory

3. Inadequate air supply

3. Check for leaks in air supply or instrument signal system; tighten loose connections

and replace leaky lines

4. Malfunctioning positioner

4. Refer to positioner User Instructions

Excessive seat

leakage

1. Improperly tightened bonnet

1. Refer to step 7.11 Assembly and Installation section for correct tightening proce-

dure

2. Worn or damaged seat ring

2. Disassemble valve and replace or repair seat ring

3. Worn or damaged seat or bonnet

gasket

3. Disassemble and replace gaskets

4. Inadequate actuator thrust

4. Check for adequate air supply to actuator; if air supply is adequate, reconfirm

service conditions and contact factory

5. Incorrectly adjusted plug

5. Refer to steps 7.9 to 7.11 Assembly and Installation section for correct plug adjust-

ment

6. Improper flow direction

6. Refer to original specifications or contact factory

7 . Improper handwheel adjust-ment

acting as a limit-stop

7. Adjust handwheel until plug seats properly

8. Worn or damaged pressure bal-

anced seals

8. Disassemble and replace pressure balanced seals

9. Inadequate air supply pressure

9. Check for leaks in air supply or instrument signal system; tighten loose connections

and replace leaky lines

Inadequate flow

1. Improper plug adjustment, limiting

stroke

1. Refer to steps 7.9 to 7.11 Assembly and Installation section for correct plug adjust-

ment

2. Malfunctioning positioner

2. Refer to positioner maintenance instructions

3. Service conditions exceed trim

design capacity

3. Verify service conditions and consult factory

4. Incorrect actuator stroke

4. Verify actuator stroke

5. Inadequate air supply pressure

5. Check for leaks in air supply or instrument signal system; tighten loose connections

and replace leaky lines

Plug slams

1. Incorrect plug adjustment al-lowing

improper cushion of air between

actuator piston and yoke

1. Refer to steps 7.9 to 7.11 Assembly and Installation section for correct plug adjust-

ment

2. Inadequate air supply

2. Check air supply to actuator; repair leaks and remove any restrictions in supply line

3. Trim sized too large for flow rate

3. Verify the service conditions and actuator sizing, install reduced trim

Valve does not fail

in correct position

1. Incorrect flow direction

1. Reconfirm direction and, if necessary, correct flow direction through valve

2. Incorrect actuator fail direction

2. Consult actuator User Manual and change fail direction

Table III: Troubleshooting Chart