Edit setpoint
Setpoint can only be edited when the setpoint parameter is displayed
in 'Custom readout 1' or 'Custom readout 2'.
To edit the setpoint press to select the readout area in which this
parameter is displayed. Press to enter the edit mode, the first digit
will lighten.
Use or to change the digits, press to select the next digit.
After the last digit is confirmed by pressing , the setpoint will be sent
to the instrument.
Use the button to exit the edit mode and cancel the changes.
i
www
You can change the setpoint edit mode into ‘step’. This enables you to
change the setpoint using fixed steps. See chapter 'Customize display
info' in section 3.2.22 of the Instruction Manual (9.17.076).
i
www
If the entered setpoint is ignored, check controller mode. See chapter
'Controller mode' in section 3.2.8 of the Instruction Manual (9.17.076).
Reset alarm
Alarm messages will be shown in the 'Top line' of the display and 'Custom
readout 2' will be selected automatically.
Enter the edit mode by pressing
. Use or to select ‘yes’ and
press again to confirm.
An alarm message will be occurring as long as the cause has not been
removed/repaired.
The button can be used to exit the edit mode and cancel the changes.
If you are not intending to reset the alarm, you can press to deactivate
'Custom readout 2'. Actual alarm messages will always been shown in the
'Top line'.
Security settings
The security settings screen allows you to define the access of the crucial
menu items of the E-8000. For every item, you can choose for enable,
disable or password. These settings can be assigned to the following
items.
Edit setpoint
Reset counter
Reset alarm
Select instrument
Settings menu
Advanced menu item
i
www
To enter the security settings from the readout screen press both and
for 5 seconds till 'enter password' display appears. The default
password is 'abc'. Please refer to 'Security settings' in section 3.4.2 of the
Instruction Manual (9.17.076) for more information.