2 flow-bus and rs232, 3 modbus, 4 profibus-dp – Bronkhorst Shut-Off Valve Control Adapter User Manual
Page 6: 5 devicenet, 6 ethercat, Flow-bus, Rs232, Odbus, Profibus-dp, Evice

BRONKHORST
2.2
FLOW-BUS
AND
RS232
Manual 9.17.024 describes the FLOW-BUS interface
Manual 9.17.027 describes the RS232 interface with FLOW-BUS protocol
Data Type
Range
read/write Secured DDE Proc/par
IO Switch Status
unsigned long
0 … 4294967295
R/W
N
288
114/31
The least significant byte of the IO Switch Status Register is used for the Shut-off Valve control adapter.
2.3
M
ODBUS
Manual 9.17.035 describes the Modbus interface
MODBUS REGISTERS
PARAMETER NAME PARAMETER TYPE ACCESS PDU ADDRESS
hex
REGISTER NUMBER
REMARK
Hex
Dec
IO Switch Status
Long Integer
RW
0xF2F8..0xF2F9 0xF2F9..0xF2FA 62201..62202
2.4
PROFIBUS-DP
Manual 9.17.025 describes the PROFIBUS-DP interface
For PROFIBUS-DP, at least version V3.3 of the GSD file bht_0586.gsd is needed.
FLOW-BUS parameter ‘IO Switch Status’ is ported to the following PRODIBUS-DP modules:
Module
Inputs
Outputs
In/Out Identifier
General Purpose IO (read)
4 byte
0x42, 0x03, 0x72, 0x1F
General Purpose IO (write)
4 byte
0x82, 0x03, 0x72, 0x1F
2.5
D
EVICE
N
ET
Manual 9.17.026 describes the DeviceNet interface
FLOW-BUS parameter ‘IO Switch Status’ is ported to the following DeviceNet object:
Analog
actuator object
Attribute
Attribute name
Service code
Data
type
Flowbus
Comment
0x32
0x64
General purpose I/O
0x0E, 0x10
INT
114, 31
General purpose I/O
2.6
E
THER
CAT
Manual 9.17.063 describes the EtherCat interface
FLOW-BUS parameter ‘IO Switch Status’ is ported to the following EtherCAT object:
Index Sub Index Description
Data Type Access PDO mapping
0x2072 0x20
IO Switch Status
Unsigned32
RW
Possible
Page 6
Operational instructions for Shut-Off Valve Control Adapter
9.17.068