Optical fibre installation instructions
II/O-Lightbus
Laying instructions for optical-fiber cable
Polymer fiber
Distances of 0.5 to 45 m
Use Beckhoff optical-fiber cable Z1101 with a 1000µm APF polymer fiber.
The bending radius of the laid cable must not be tighter than 30mm.
The laid optical-fiber cable must not be shorter than 0.5 meters and not
longer than 45 meters.
Glass fiber
Distances up to 1000 m
For greater distances glass fiber cables can be used with a length of up to
1000 meters.
Glass fiber cables can be supplied in various lengths with assembled
connectors.