beautypg.com

Laying instructions for optical-fiber cable, Polymer fiber, Glass fiber – BECKHOFF II/O-Lightbus User Manual

Page 4

background image

Eiserstr. 5, D-33415 Verl, Germany, Phone +495246/963-0, Fax +495246/963-149

3

Optical fibre installation instructions

II/O-Lightbus

Laying instructions for optical-fiber cable


Polymer fiber

Distances of 0.5 to 45 m

Use Beckhoff optical-fiber cable Z1101 with a 1000µm APF polymer fiber.

The bending radius of the laid cable must not be tighter than 30mm.

The laid optical-fiber cable must not be shorter than 0.5 meters and not
longer than 45 meters.

Glass fiber

Distances up to 1000 m

For greater distances glass fiber cables can be used with a length of up to
1000 meters.

Glass fiber cables can be supplied in various lengths with assembled
connectors.