beautypg.com

Technical data – BECKHOFF M1600 User Manual

Page 6

background image

M1600 Parallel Input/Output

Beckhoff II/O-System

Page 6 of 14

Version : 2.0

Date : 8.8.94

3. Technical Data

Inputs / Outputs

16, can be configured for each port;
8 high current outputs

LED shows

state of all inputs / outputs

input specifications

24 VDC, 10 mA, digital filter

input switching voltages

0 - 8V = LOW
15 - 24V = HIGH

input delay

0,7 ms RC network
6,8 ms input latch

Output specifications

normal i/o :
24 VDC, max. 500 mA, short circuit proof

High current :
24 VDC, max. 2 A, short circuit proof

Output check

watchdog system 100ms

Connections

can be connected for 16 I/O; +,-,signal
and 8 high current outputs, +,-

Data connection

fibre optic II/O system

transmission rate

2,5 MBaud, 25 µs for 32 Bit

Supply Voltage

24 VDC (± 10%)

Input Current

0,1 A (without load and input currents)

Cartridge

closed, can be installed to cartridge carrier
according to DIN EN 50022, 50035

Size (B * W * D)

270 * 76 * 68 mm

Weight

about 1100 g

Working Temperature

±0..+55 øC

Storage Temperature

-20..+70 øC