Technical data – BECKHOFF M1600 User Manual
Page 6

M1600 Parallel Input/Output
Beckhoff II/O-System
Page 6 of 14
Version : 2.0
Date : 8.8.94
3. Technical Data
Inputs / Outputs
16, can be configured for each port;
8 high current outputs
LED shows
state of all inputs / outputs
input specifications
24 VDC, 10 mA, digital filter
input switching voltages
0 - 8V = LOW
15 - 24V = HIGH
input delay
0,7 ms RC network
6,8 ms input latch
Output specifications
normal i/o :
24 VDC, max. 500 mA, short circuit proof
High current :
24 VDC, max. 2 A, short circuit proof
Output check
watchdog system 100ms
Connections
can be connected for 16 I/O; +,-,signal
and 8 high current outputs, +,-
Data connection
fibre optic II/O system
transmission rate
2,5 MBaud, 25 µs for 32 Bit
Supply Voltage
24 VDC (± 10%)
Input Current
0,1 A (without load and input currents)
Cartridge
closed, can be installed to cartridge carrier
according to DIN EN 50022, 50035
Size (B * W * D)
270 * 76 * 68 mm
Weight
about 1100 g
Working Temperature
±0..+55 øC
Storage Temperature
-20..+70 øC