14 light curtain (category 4, pl e) – BECKHOFF TwinSAFE User Manual
Page 87

Circuit examples
Application Guide TwinSAFE
85
2.14 Light curtain (Category 4, PL e)
The light curtain has two OSSD outputs (Output-Signal-Switching-Device), which are wired to safe inputs
of an EL1904. The testing of the inputs is not active, since the OSSD outputs carry out their own test.
Furthermore, the signals are checked for discrepancy (200 ms). The feedback loop is read via a safe
input. Testing is active for this input. The contactors K1 and K2 are connected in parallel to the safe
output. Current measurement and testing of the output are active for this circuit.
Logical connection in
the EL6900
K1
K2
K1
K2
OSSD 1
OSSD 2
2.14.1 Parameters of the safe input and output terminals
EL1904
Parameter
Value
Sensor test channel 1 active
No
Sensor test channel 2 active
No
Sensor test channel 3 active
Yes
Sensor test channel 4 active
Yes
Logic channel 1 and 2
OSSD asynchronous analysis
Logic channel 3 and 4
Single Logic
EL2904
Parameter
Value
Current measurement active
Yes
Output test pulses active
Yes